2022-11-14 16:07:24RESIDENTIAL (R3) FIFTH BUILDING REVIEW COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 SUBMITTAL #22021383
 310 DYER RD
  
 ORIGINAL COMMENT:
 7- HURRICANE SHUTTERS:
 PROVIDE COMPLETE INSTALLATION SCHEDULE. SEE CITY
 SAMPLE.
  
 PREVIOUS COMMENT:
 REPEAT COMMENT. NOT ADDRESSED. NEED TO PROVIDE THE
 INSTALLATION SCHEDULE.
 NOTE: THERE ARE TWO DIFFERENT PRODUCT APPROVALS
 SUBMITTED. SUBMIT EITHER THE COMPLETE FLORIDA PRODUCT
 APPROVAL FL15208-R6 INCLUDING THE INSTALLATION
 INSTRUCTIONS OR THE MIAMI DADE NOA 20-1102.08.
  
 RESPONSE:
 7(A)INFORMATION SUBMITTED UNDER FLORIDA PRODUCT
 APPROVAL FL15208-R6 DOESN'T MATCH INSTALLATION
 INSTRUCTIONS DRAWINGS THAT CORRESPOND TO THIS FLORIDA
 PRODUCT APPROVAL. PLEASE DON'T MISMATCH INSTALLATION
 INSTRUCTIONS. SUBMIT EITHER THE INSTALLATION
 INSTRUCTIONS CORRESPONDING TO THIS FLORIDA PRODUCT
 APPROVAL OR SUBMIT COMPLETE NOA 20-1102.08.
 SEC. 107.2.1 CITY AMENDMENTS.
  
 7(B)REVISE SHUTTERS INSTALLATION SCHEDULE:
 (1)OPENINGS LOCATED WITHIN 4 FEET OF THE END OF THE
 STRUCTURE ARE CONSIDERED END ZONE 5. REVISE THE DESIGN
 PRESSURES FOR OPENINGS LOCATED IN THE END ZONE. FOR
 EXAMPLE OPENING #105G IS LOCATED IN THE END ZONE.
 NOTE: DESIGN PRESSURES SHOWN ON THE PROPOSED ELEVATIONS
 ARE TOO LOW. SEE COMPONENTS & CLADDING PRESSURES BELOW
 THE ELEVATION NOTES AND REVISE AS REQUIRED. CHECK ALL
 OPENINGS TO AVOID DELAYS.
 SEC. R301.2.1 FBC-RESIDENTIAL.
  
 (2)REVISE DESIGN PRESSURES ON THE SHUTTERS INSTALLATION
 SCHEDULE TO MATCH REVISED DESIGN PRESSURES. SEE ITEM
 ABOVE. CHECK ALL OPENINGS TO AVOID DELAYS.
 SEC. R301.2.1 FBC-RESIDENTIAL.
  
 (3)INFORMATION ON SHUTTER MOUNTING IS INCORRECT.
 CORRECT SHUTTER MOUNTING IS EITHER THE "WALL MOUNT
 CONDITION", "INTERIOR MOUNT CONDITION", ETC. SEE
 MOUNTING CONDITIONS ON PAGE 2 OF NOA SUBMITTED AND
 REVISE AS REQUIRED.
 SEC. 107.2.1 CITY AMENDMENTS.
  
 (4)NEED TO COMPLETE THE SHUTTERS GLASS SEPARATION
 COLUMN. SEE PRODUCT APPROVAL FOR REQUIRED SEPARATION.
 SEC. 107.2.1 CITY AMENDMENTS.
  
 (3)NEED TO COMPLETE THE ANCHOR SPACING COLUMN. SPECIFY
 ANCHOR SPACING AT TOP AND BOTTOM.
 SEC. R301.2.1 FBC-RESIDENTIAL.
  
 8-ARCHITECT OF RECORD TO APPROVE ABOVE PRODUCT
 APPROVALS AS REQUIRED BY SEC. 107.3.4.1 CITY
 AMENDMENTS.
  
 PREVIOUS COMMENT:
 9- BALUSTER DETAILS #6 ON SHEET A-431 SHOWS A 6 INCH
 SPHERE AT THE BOTTOM OF THE GUARD. THIS DOESN'T COMPLY
 WITH SEC. R312.1.3 FBC-RESIDENTIAL. REVISE AS REQUIRED.
 ALSO. SEC. R312.1.3 FBC-RESIDENTIAL REQUIRES THAT NOT
 OPENING SHALL ALLOW THE PASSAGE OF A 4 INCH SPHERE.
 DETAIL SPECIFIES 4" SPHERE. DIMENSION HAS TO BE LESS
 THAN 4". REVISE DIMENSION AS REQUIRED.
 NOTE: THIS NOTE ALSO APPLIES TO THE OPENING EXCEPTION
 #1, WHERE THE TRIANGULAR AREA FORMED BY THE RISER,
 THREAD AND BOTTOM OF THE GUARDRAIL DOESN'T ALLOW THE
 PASSAGE OF A 6 INCH SPHERE. REVISE THIS TRIANGULAR
 DIMENSION AS WELL.
 REVISE ALL STAIR DETAILS AS REQUIRED.
  
 RESPONSE:
 DETAILS STILL SHOW 4" AND 6" OPENINGS. THIS ITEM WAS
 SPECIFICALLY DISCUSSED IN PERSON WITH CALEB LAUX
 (ARCH.). I TOLD HIM DIMENSIONS NEED TO BE LESS THAN 4"
 AND 6" RESPECTIVELY. REVISE DIMENSIONS AS REQUIRED.
  
 PREVIOUS COMMENT:
 10-ADDITIONAL COLONIAL SHUTTERS FL6414-R6 WAS
 SUBMITTED.
 PROVIDE COMPLETE INSTALLATION SCHEDULE. SEE CITY
 SAMPLE.
  
 RESPONSE:
 INFORMATION ON SHUTTERS INSTALLATION SCHEDULE IS
 INCOMPLETE. NEED TO FILL ALL THE COLUMNS.
 NOTE: COORDINATE WITH COMMENTS ON ITEM #7 ABOVE. UNABLE
 TO IDENTIFY PROPOSED INSTALLATION. CLEARLY IDENTIFY
 CONNECTION TYPES AND DETAILS ON SHEET 4 AND 7 OF
 PRODUCT APPROVAL SUBMITTED. CHECK THE SHUTTER SPAN
 BASED ON THE OPENING SIZE. ALSO, CHECK MAXIMUM SPAN
 BETWEEN STORM BARS.
 SEC. R301.2.1 FBC-RESIDENTIAL. SEC. 107.2.1 CITY
 AMENDMENTS.
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT WITH A DESCRIPTION OF THE
 REVISION MADE WILL HELP TO EXPEDITE THE REVIEW PROCESS.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER