| 2022-09-26 12:33:59 | RESIDENTIAL (R3) PRODUCT APPROVALS FOURTH SUBMITTAL |
| | BUILDING REVIEW COMMENTS |
| | CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS. |
| | SUBMITTAL #22021383 |
| | 310 DYER RD |
| | |
| | 1- OK. |
| | 2- OK. |
| | 3- OK. |
| | 4- OK. |
| | 5- OK |
| | 6- OK. |
| | |
| | ORIGINAL COMMENT: |
| | 7- HURRICANE SHUTTERS: |
| | PROVIDE COMPLETE INSTALLATION SCHEDULE. SEE CITY |
| | SAMPLE. |
| | |
| | RESPONSE: |
| | REPEAT COMMENT. NOT ADDRESSED. NEED TO PROVIDE THE |
| | INSTALLATION SCHEDULE. |
| | NOTE: THERE ARE TWO DIFFERENT PRODUCT APPROVALS |
| | SUBMITTED. SUBMIT EITHER THE COMPLETE FLORIDA PRODUCT |
| | APPROVAL FL15208-R6 INCLUDING THE INSTALLATION |
| | INSTRUCTIONS OR THE MIAMI DADE NOA 20-1102.08. |
| | |
| | 8-ARCHITECT OF RECORD TO APPROVE ABOVE PRODUCT |
| | APPROVALS AS REQUIRED BY SEC. 107.3.4.1 CITY |
| | AMENDMENTS. |
| | |
| | PREVIOUS COMMENT: |
| | 9- BALUSTER DETAILS #6 ON SHEET A-431 SHOWS A 6 INCH |
| | SPHERE AT THE BOTTOM OF THE GUARD. THIS DOESN'T COMPLY |
| | WITH SEC. R312.1.3 FBC-RESIDENTIAL. REVISE AS REQUIRED. |
| | ALSO. SEC. R312.1.3 FBC-RESIDENTIAL REQUIRES THAT NOT |
| | OPENING SHALL ALLOW THE PASSAGE OF A 4 INCH SPHERE. |
| | DETAIL SPECIFIES 4" SPHERE. DIMENSION HAS TO BE LESS |
| | THAN 4". REVISE DIMENSION AS REQUIRED. |
| | NOTE: THIS NOTE ALSO APPLIES TO THE OPENING EXCEPTION |
| | #1, WHERE THE TRIANGULAR AREA FORMED BY THE RISER, |
| | THREAD AND BOTTOM OF THE GUARDRAIL DOESN'T ALLOW THE |
| | PASSAGE OF A 6 INCH SPHERE. REVISE THIS TRIANGULAR |
| | DIMENSION AS WELL. |
| | REVISE ALL STAIR DETAILS AS REQUIRED. |
| | |
| | RESPONSE: |
| | REPEAT COMMENT. NOT ADDRESSED. |
| | |
| | NEW COMMENT: |
| | 10-ADDITIONAL COLONIAL SHUTTERS FL6414-R6 WAS |
| | SUBMITTED. |
| | PROVIDE COMPLETE INSTALLATION SCHEDULE. SEE CITY |
| | SAMPLE. |
| | |
| | |
| | WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE |
| | ORIGINAL REVIEW COMMENT WITH A DESCRIPTION OF THE |
| | REVISION MADE WILL HELP TO EXPEDITE THE REVIEW PROCESS. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY |
| | QUESTIONS REGARDING THESE COMMENTS, |
| | JULIO GOMEZ |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | BUILDING DIVISION |
| | (561)805-6712 |
| | [email protected] |