| 2022-07-13 16:26:55 | RESIDENTIAL (R3) PRODUCT APPROVALS THIRD SUBMITTAL |
| | BUILDING REVIEW COMMENTS |
| | CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS. |
| | SUBMITTAL #22021383 |
| | |
| | 1- CEDAR ROOF SHINGLES: |
| | |
| | ORIGINAL COMMENT: |
| | A)PROVIDE CURRENT (2020 CODE VERSION) PRODUCT APPROVAL |
| | AS REQUIRED BY FAC 61G20.3.001. |
| | |
| | RESPONSE: |
| | REPEAT COMMENT. FLORIDA PRODUCT APPROVAL FL7993-R1 |
| | SUBMITTED IS FOR 2017 CODE VERSION. NEED PRODUCT |
| | APPROVAL FOR CURRENT 2020 CODE VERSION. CHAPTER 553 |
| | F.S. |
| | NOTE: WOOD SHINGLES NEED TO COMPLY WITH THE |
| | REQUIREMENTS OF SEC. R905.7 FBC-RESIDENTIAL. CHECK IF |
| | THE ALLOWABLE UPLIFT RESISTANCE STATED IN THE PRODUCT |
| | APPROVAL MEETS THE UPLIFT REQUIREMENTS FOR THIS HOUSE |
| | TO AVOID CONFLICTS/DELAYS. |
| | |
| | ORIGINAL COMMENT: |
| | B)PROVIDE COMPLETE AND CURRENT PRODUCT APPROVAL. FAC |
| | 61G20.3.001. |
| | INFORMATION UPLOADED TO PROJECTDOX IS INCOMPLETE. |
| | COMPLETE PRODUCT APPROVAL INCLUDES THE FLORIDA PRODUCT |
| | APPROVAL COVER PAGE SHOWING THE CODE VERSION AND |
| | INSTALLATION INSTRUCTIONS INCLUDED IN THE PRODUCT |
| | APPROVAL. |
| | |
| | RESPONSE: |
| | FLORIDA PRODUCT APPROVAL FL7993-R1 SUBMITTED IS FOR |
| | 2017 CODE VERSION. NEED PRODUCT APPROVAL FOR CURRENT |
| | 2020 CODE VERSION. |
| | ALSO, INFORMATION SUBMITTED DOESN'T CORRESPOND TO |
| | FLORIDA PRODUCT APPROVAL FL7993-R1 AND IS TOO OLD TO BE |
| | USED WITH CURRENT CODE. |
| | NOTE: WOOD SHINGLES NEED TO COMPLY WITH THE |
| | REQUIREMENTS OF SEC. R905.7 FBC-RESIDENTIAL. CHECK IF |
| | THE ALLOWABLE UPLIFT RESISTANCE STATED IN THE PRODUCT |
| | APPROVAL MEETS THE UPLIFT REQUIREMENTS FOR THIS HOUSE |
| | TO AVOID CONFLICTS/DELAYS. |
| | |
| | ORIGINAL COMMENT: |
| | 2- SKYLIGHT. PROVIDE COMPLETE AND CURRENT PRODUCT |
| | APPROVAL. FAC 61G20.3.001. |
| | INFORMATION UPLOADED TO PROJECTDOX IS INCOMPLETE. |
| | COMPLETE PRODUCT APPROVAL INCLUDES THE FLORIDA PRODUCT |
| | APPROVAL COVER PAGE SHOWING THE CODE VERSION AND |
| | INSTALLATION INSTRUCTIONS INCLUDED IN THE PRODUCT |
| | APPROVAL. |
| | |
| | RESPONSE: |
| | PARTIALLY DONE. FLORIDA PRODUCT APPROVAL COVER PAGE FOR |
| | FL13303-R10 WAS SUBMITTED. |
| | HALLMARK CERTIFICATE OF CONFORMANCE AND LICENSE (CCL) |
| | SUBMITTED DOESN'T MEET THE DESIGN PRESSURES CALCULATED |
| | BY THE ARCHITECT OF RECORD AND DOESN'T CORRESPOND TO |
| | FLORIDA PRODUCT APPROVAL FL13303-R10. NEED TO PROVIDE |
| | PRODUCT APPROVAL THAT MEETS OR EXCEEDS THE CALCULATED |
| | DESIGN PRESSURES. |
| | ALSO, NEED TO SUBMIT THE INSTALLATION INSTRUCTIONS |
| | CORRESPONDING TO THIS PRODUCT APPROVAL. |
| | |
| | 3- WINDOW MULLIONS: |
| | A)OK. |
| | |
| | ORIGINAL COMMENT: |
| | B)PROVIDE COMPLETE AND CURRENT PRODUCT APPROVAL. FAC |
| | 61G20.3.001. |
| | INFORMATION UPLOADED TO PROJECTDOX IS INCOMPLETE. |
| | COMPLETE PRODUCT APPROVAL INCLUDES THE FLORIDA PRODUCT |
| | APPROVAL COVER PAGE SHOWING THE CODE VERSION (2020) AND |
| | INSTALLATION INSTRUCTIONS INCLUDED IN THE PRODUCT |
| | APPROVAL. |
| | |
| | RESPONSE: |
| | REPEAT COMMENT. CORRESPONDING FLORIDA PRODUCT APPROVAL |
| | COVER WAS NOT SUBMITTED. |
| | |
| | ORIGINAL COMMENT: |
| | 4-CASEMENT WINDOWS. |
| | PROVIDE COMPLETE AND CURRENT PRODUCT APPROVAL. FAC |
| | 61G20.3.001. |
| | INFORMATION UPLOADED TO PROJECTDOX IS INCOMPLETE. |
| | COMPLETE PRODUCT APPROVAL INCLUDES THE FLORIDA PRODUCT |
| | APPROVAL COVER PAGE SHOWING THE CODE VERSION AND |
| | INSTALLATION INSTRUCTIONS INCLUDED IN THE PRODUCT |
| | APPROVAL. |
| | |
| | RESPONSE: |
| | REPEAT COMMENT. CORRESPONDING FLORIDA PRODUCT APPROVAL |
| | COVER WAS NOT SUBMITTED. |
| | |
| | ORIGINAL COMMENT: |
| | 5-DOUBLE HUNG WINDOWS. |
| | PROVIDE COMPLETE AND CURRENT PRODUCT APPROVAL. FAC |
| | 61G20.3.001. |
| | INFORMATION UPLOADED TO PROJECTDOX IS INCOMPLETE. |
| | COMPLETE PRODUCT APPROVAL INCLUDES THE FLORIDA PRODUCT |
| | APPROVAL COVER PAGE SHOWING THE CODE VERSION AND |
| | INSTALLATION INSTRUCTIONS INCLUDED IN THE PRODUCT |
| | APPROVAL. |
| | |
| | RESPONSE: |
| | REPEAT COMMENT. CORRESPONDING FLORIDA PRODUCT APPROVAL |
| | COVER WAS NOT SUBMITTED. |
| | |
| | ORIGINAL COMMENT: |
| | 6-EXTERIOR DOORS. |
| | PROVIDE COMPLETE AND CURRENT PRODUCT APPROVAL. FAC |
| | 61G20.3.001. |
| | INFORMATION UPLOADED TO PROJECTDOX IS INCOMPLETE. |
| | COMPLETE PRODUCT APPROVAL INCLUDES THE FLORIDA PRODUCT |
| | APPROVAL COVER PAGE SHOWING THE CODE VERSION AND |
| | INSTALLATION INSTRUCTIONS INCLUDED IN THE PRODUCT |
| | APPROVAL. |
| | |
| | RESPONSE: |
| | REPEAT COMMENT. CORRESPONDING FLORIDA PRODUCT APPROVAL |
| | COVER WAS NOT SUBMITTED. |
| | |
| | ORIGINAL COMMENT: |
| | 7- HURRICANE SHUTTERS: |
| | PROVIDE COMPLETE INSTALLATION SCHEDULE. SEE CITY |
| | SAMPLE. |
| | |
| | RESPONSE: |
| | REPEAT COMMENT. NOT ADDRESSED. |
| | |
| | 8-ARCHITECT OF RECORD TO REVIEW/APPROVE ALL PRODUCT |
| | APPROVALS AS REQUIRED BY SEC. 107.3.4.1 CITY |
| | AMENDMENTS. |
| | NOTE: THIS APPLIES WHEN RESUBMITTING A NEW PRODUCT |
| | APPROVAL. |
| | |
| | NEW COMMENT BASED ON NEW STAIRWAY DRAWINGS SUBMITTED: |
| | 9- BALUSTER DETAILS #6 ON SHEET A-431 SHOWS A 6 INCH |
| | SPHERE AT THE BOTTOM OF THE GUARD. THIS DOESN'T COMPLY |
| | WITH SEC. R312.1.3 FBC-RESIDENTIAL. REVISE AS REQUIRED. |
| | NOTE: SEC. R312.1.3 FBC-RESIDENTIAL REQUIRES THAT NOT |
| | OPENING SHALL ALLOW THE PASSAGE OF A 4 INCH SPHERE. |
| | TYPICALLY, THE OPENING IS SPECIFIED WITH A DIMENSION |
| | LESS THAN 4 INCH TO COMPLY WITH THIS REQUIREMENT. |
| | THIS NOTE ALSO APPLIES TO THE OPENING EXCEPTION #1, |
| | WHERE THE TRIANGULAR AREA FORMED BY THE RISER, THREAD |
| | AND BOTTOM OF THE GUARDRAIL DOESN'T ALLOW THE PASSAGE |
| | OF A 6 INCH SPHERE. REVISE THIS TRIANGULAR DIMENSION AS |
| | WELL. |
| | REVISE ALL STAIR DETAILS AS REQUIRED. |
| | |
| | WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE |
| | ORIGINAL REVIEW COMMENT WITH A DESCRIPTION OF THE |
| | REVISION MADE WILL HELP TO EXPEDITE THE REVIEW PROCESS. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |