| 2022-03-26 11:49:06 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. A COMPREHENSIVE PLAN REVIEW COULD NOT BE COMPLETED |
| | AT THIS TIME. NO ELECTRICAL PLAN HAS BEEN SUBMITTED, |
| | ONLY SPECIFICATIONS FROM MANUFACTURER. PLEASE PROVIDE |
| | ELECTRICAL PLAN SIGNED BY ELECTRICAL CONTRACTOR |
| | QUALIFIER, OR SIGNED/SEALED BY DESIGN PROFESSIONAL. TO |
| | INCLUDE WIRE SIZES, ANY REQUIRED DISCONNECTING MEANS |
| | FOR MOTORS, OVERCURRENT PROTECTION, AND LOAD |
| | CALCULATION AND ONE-LINE DIAGRAM OF EXISTING SERVICE TO |
| | INCLUDE BOTH NEW AND EXISTING LOADS.FBC 107.2.1 NEC 220 |
| | FS 471.003(2)(H); 471.025; WPB FBC 107.1 |
| | |
| | 2. PROVIDE CUT SHEETS FOR PRODUCT APPROVAL OF VACCUM |
| | SYSTEM SHOWING UL LISTING OR OTHER NRTL LISTING. NEC |
| | 110.2 110.3B |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | CODES IN EFFECT: |
| | |
| | HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B |
| | UILDING-PERMIT-FORMS |
| | |
| | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE 2020 7TH ED. |
| | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020 |
| | 7TH EDITION |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 |
| | 7TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION |
| | NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | V/R, |
| | |
| | FRANK GIAQUINTO III |
| | ELECTRICAL INSPECTOR |
| | ELECTRICAL PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | [email protected] |
| | CELL: 561-805-6744 |
| | |