| Plan Review Notes For Permit 22021367 |
| Permit Number |
22021367 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2022-03-22 09:09:02 | ROOFING SYSTEM | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected] | | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | | AMENDMENT | | | | | | CORRECTIONS NEEDED - | | | | | | 1) PLEASE CIRCLE THE ROOFING SYSTEM TO BE USED IN THE | | | PRODUCT APPROVAL - THE SYSTEM WILL NEED TO MEET THE | | | REQUIRED PRESSURES SHOWN ON DRAWING S-0.10 FROM THE | | | BUILDING DESIGNER. | | | | | | 2) ALL PRODUCT APPROVALS NEED TO BE REVIEWED AND MARKED | | | APPROVED BY THE BUILDING DESIGNER OF RECORD FBC WPB | | | 107.3.4 | | | | | | 3) PLEASE PROVIDE A COPY OF THE PRODUCT APPROVAL FOR | | | THE LIGHT WEIGHT CONCRETE FBC 1917.2.1 | | | APPLICATION OF ALL LIGHTWEIGHT INSULATING CONCRETE ROOF | | | DECKS SHALL BE BY APPLICATORS APPROVED BY THE | | | LIGHT-WEIGHT INSULATING CONCRETE DECK MANUFACTURER. | | | PRODUCT APPROVAL SHALL BE REQUIRED FOR ALL LIGHTWEIGHT | | | INSULATING CONCRETE SYSTEMS. | | | |
|