| 2022-08-10 16:35:37 | INSUFFICIENT |
| | |
| | 1) PROVIDE A SURVEY, PREPARED BY A FLORIDA LICENSED |
| | SURVEYOR, THAT SHOWS THE RIGHT-OF-WAY LINE, THE |
| | SIDEWALK, AND ANY TREES WITHIN THE RIGHT-OF-WAY ALONG |
| | THE FIBER CONDUIT PATH SO THAT STAFF CAN VERIFY THAT |
| | THE BORE AND ANY REQUIRED BORE PITS AND HANDHOLES ARE |
| | WITHIN THE RIGHT-OF-WAY. THE SURVEY NEEDS TO INCLUDE |
| | THE LOCATION OF PROPOSED HANDHOLES 00+00, 01+10 AND THE |
| | BORE SECTION ALONG THE WEST SIDE OF SOUTH DIXIE HIGHWAY |
| | SINCE A SURVEY THAT THE CITY HAS ON FILE SHOWS THAT THE |
| | AREA BETWEEN THE FENCE AND THE SIDEWALK AS PRIVATE |
| | PROPERTY, NOT RIGHT-OF-WAY. IN ORDER TO INSTALL |
| | HANDHOLES AND BORE UNDER PRIVATE PROPERTY IS MUST BE IN |
| | A GENERAL UTILITY EASEMENT. THIS GENERAL UTILITY |
| | EASEMENT MUST BE CLEARLY SHOWN ON THE SURVEY. |
| | |
| | 2) THE TUBULAR MARKERS ARE NOT PERMITTED. MARKERS MAY |
| | ONLY BE INSTALLED WITHIN THE HANDHOLES OR OTHERWISE |
| | BURIED. |
| | |
| | 3) THE PLANS MUST SHOW THE DIMENSION BETWEEN THE PALM |
| | TREE AND THE EXCAVATION FOR HANDHOLE 04+55 OF AT LEAST |
| | THREE FEET FROM THE TRUNK OF THE PALM TREE. |
| | ADDITIONALLY, TO PROTECT THE PALM TREE TRUNK FROM |
| | DAMAGE, THE BORE MUST COME FROM THE WEST. THE BORE |
| | MACHINE MAY NOT STAGE ADJACENT TO THE PALM TREE. |
| | |
| | 4) THE BORE DEPTH IS SUFFICIENT TO AVOID TREE ROOTS. |
| | |
| | CONTACT ERIC SCHNEIDER @ (561) 822-1446 |
| | [email protected] |
| | |