| 2022-03-10 08:30:34 | JONATHAN BROOKS JR. |
| | BUILDING PLANS EXAMINER |
| | WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM |
| | PHONE (561) 805-6656 |
| | EMAIL: [email protected] |
| | |
| | 1ST REVIEW: FBC 2020 7TH EDITION |
| | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) |
| | FBC B = FBC BUILDING |
| | FBC R = FBC RESIDENTIAL |
| | FBC EB = FBC EXISTING BUILDING |
| | FBC A = FBC ACCESSIBILITY |
| | FBC EC = FBC ENERGY CONSERVATION |
| | WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC |
| | RESULTS: DENIED |
| | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| | TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT |
| | CITY HALL, OR EMAIL [email protected]. |
| | |
| | 1. FBC R 301 FAC9N-3 FLORIDA STATE PRODUCT APPROVAL |
| | FL16709-R9 IS INCOMPLETE, PROVIDE THE FOLLOWING |
| | ADDITIONAL INFORMATION: EVALUATION REPORT PAGES 1-4 TO |
| | INCLUDE LIMITATIONS PAGE(S). THE EVALUATION REPORTS CAN |
| | BE PRINTED FROM THE SUMMARY OF PRODUCTS LOCATED AT THE |
| | BOTTOM OF THE COVER PAGE. PRINT PAGES 1-4 ONLY. |
| | 2. FBC R 301 FAC9N-3 SUBMITTED FLORIDA DBPR PRODUCT |
| | APPROVAL FL16709-R9 COVERS MULTIPLE ROOF SYSTEM TYPES |
| | A-2 THROUGH E, NO. W-1 THRU W-5. PLEASE SELECT SYSTEM |
| | NO.; EXPOSURE; ENCLOSURE; ROOF HEIGHT; ZONE AND |
| | ULTIMATE WIND SPEED. THE CORRECT EXPOSURE FOR THE |
| | LISTED ADDRESS IS EXPOSURE D. PRODUCT APPROVAL |
| | FL16709-R9 WILL NOT SATISFY EXPOSURE CATEGORY D |
| | ENCLOSED AREAS WITHOUT USING INSULATION OR PROVIDING |
| | ENGINEERED ENHANCED NAILING. ALL APPLICABLE DETAILS AND |
| | ATTACHMENTS MUST BE CLEARLY IDENTIFIED ON THE PRODUCT |
| | APPROVAL DRAWINGS. DETAILS AND ATTACHMENTS NOT |
| | SPECIFICALLY COVERED IN PRODUCT APPROVALS WILL NEED |
| | SITE-SPECIFIC ENGINEERING. |
| | 3. FBC R 301 FAC9N-3 FLORIDA STATE PRODUCT APPROVAL |
| | FL14826-R6 IS INCOMPLETE, PROVIDE THE FOLLOWING |
| | ADDITIONAL INFORMATION: EVALUATION REPORT PAGES 1-7 TO |
| | INCLUDE LIMITATIONS PAGE(S). THE EVALUATION REPORTS CAN |
| | BE PRINTED FROM THE SUMMARY OF PRODUCTS LOCATED AT THE |
| | BOTTOM OF THE COVER PAGE. PRINT PAGES 1-7 ONLY. |
| | 4. FBC R 301 FAC9N-3 SUBMITTED STATE OF FLORIDA PRODUCT |
| | APPROVAL FL14826-R6 COVERS MULTIPLE SUBSTRATES AND |
| | REQUIRED ANCHORS TO ACHIEVE THE REQUIRED DESIGN |
| | PRESSURES. SELECT SUBSTRATE AND REQUIRED ANCHORS FROM |
| | PAGE #1 OF THE INSTALLATION ANCHORAGE DETAILS. ALL |
| | APPLICABLE DETAILS AND ATTACHMENTS MUST BE CLEARLY |
| | IDENTIFIED ON THE PRODUCT APPROVAL DRAWINGS. DETAILS |
| | AND ATTACHMENTS NOT SPECIFICALLY COVERED IN PRODUCT |
| | APPROVALS WILL NEED SITE-SPECIFIC ENGINEERING. |
| | 5. SUBMITTED PRODUCT APPROVAL FL18355-R6 HAS BEEN |
| | REVISED TO FL18355-R7. PLEASE PROVIDE A COMPLETE SET. |
| | ALL APPLICABLE DETAILS AND ATTACHMENTS MUST BE CLEARLY |
| | IDENTIFIED ON THE PRODUCT APPROVAL DRAWINGS. DETAILS |
| | AND ATTACHMENTS NOT SPECIFICALLY COVERED IN PRODUCT |
| | APPROVALS WILL NEED SITE-SPECIFIC ENGINEERING. AS PER |
| | RULE 61G20-3 |
| | 6. SUBMITTED PRODUCT APPROVAL FL10450-R14 HAS BEEN |
| | REVISED TO FL10450-R15. PLEASE PROVIDE A COMPLETE SET. |
| | ALL APPLICABLE DETAILS AND ATTACHMENTS MUST BE CLEARLY |
| | IDENTIFIED ON THE PRODUCT APPROVAL DRAWINGS. DETAILS |
| | AND ATTACHMENTS NOT SPECIFICALLY COVERED IN PRODUCT |
| | APPROVALS WILL NEED SITE-SPECIFIC ENGINEERING. AS PER |
| | RULE 61G20-3. |
| | 7. FBC B 107.2.1 FOR CLARITY PLEASE REVISE ROOF |
| | DIAGRAM/SKETCH AND INCLUDE FLAT ROOF SLOPE(S). FLAT/LOW |
| | SLOPE ROOFS MUST SHOW POSITIVE DRAINAGE. |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMEMTS. |
| | |