| Plan Review Notes For Permit 22021281 |
| Permit Number |
22021281 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2022-02-28 14:43:01 | FIRE PROVISO COMMENTS: | | | (1) AUDIBLE DEVICES PROVIDED FOR SLEEPING AREAS SHALL | | | PRODUCE A LOW FREQUENCY SIGNAL COMPLIANT WITH NFPA 72 | | | 18.4.5.3 | | | (2) PROVIDE A RECORD OF COMPLETION AFTER INSTALLATION | | | AND TESTING TO THE FIRE INSPECTOR, PER NFPA 72 7.2 | | | (3) A BATTERY TEST SHALL BE CONDUCTED AND WITNESSED BY | | | THE FIRE INSPECTOR IN ACCORDANCE WITH NFPA 72, 14.4 | | | |
|