| 2022-07-26 10:09:42 | WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION |
| | SERVICES/ BUILDING DIVISION |
| | 2020 FBC- BUILDING PLAN REVIEW |
| | W. P. B. REVISION: 22021250 |
| | W. P. B. PERMIT: 21021446 |
| | ADD: 3114 TUXEDO AVE. |
| | CONT: S. MACDONALD CONTRACTING |
| | TEL: 561-689-8848 |
| | E-MAIL: [email protected] |
| | |
| | 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | 3RD REVIEW |
| | DATE: TUES. JULY 26TH/2022 |
| | ACTION: DENIED |
| | |
| | 1) THE SHEET C-2 THE SITE PLAN & C3 ENLARGED SITE PLAN: |
| | 1A) 2ND REQUEST. PLEASE NOTE THE SAME PLAN CAN BE USED |
| | BUT A SEPARATE PERMIT IS REQUIRED FOR STRIPING OF THE |
| | PARKING LOT. ALSO NOTE COMMENT 1B-1D WILL BE REVIEWED |
| | UNDER THE STRIPING PERMIT. FEES WILL NEED TO BE |
| | ADJUSTED SO SOME OF THE FUNDS GO TOWARDS THE EXTERIOR |
| | SITE WORK. PLEASE NOTE IF NO NEW PLANS ARE SUBMITTED |
| | FOR THE SITE WORK THEN THE CORRECTIONS WILL NEED TO |
| | SHOWN UNDER THE MASTER PERMIT/ REVISION. IF THE |
| | EXTERIOR SITE WORK IS TO BE SHOWN UNDER THIS REVISION, |
| | ON BOTH THE REVISION SHEET AND C1 COVER SHEET THE |
| | PROJECT DESCRIPTION WILL ALSO NEED TO BE UPDATED. |
| | CURRENTLY THE SCOPE OF WORK STATES INTERIOR BUILD-OUT |
| | OF EXISTING OPEN SPACE STRUCTURE, (PREVIOUSLY USE AS |
| | OFFICES). |
| | |
| | 1ST ROUND COMMENT. A SEPARATE PERMIT IS REQUIRED FOR |
| | THE STRIPING OF THE PARKING LOT AND REQUIRED ACCESSIBLE |
| | PARKING SPACES AND ACCESS AISLES. 2020 |
| | FBC-ACCESSIBILITY CODE SECTION ACCESSIBLE PARKING |
| | SPACES. 208.3. LOCATION. |
| | PARKING SPACES COMPLYING WITH 502 THAT SERVE A |
| | PARTICULAR BUILDING OR FACILITY SHALL BE LOCATED ON THE |
| | SHORTEST ACCESSIBLE ROUTE FROM PARKING TO AN ENTRANCE |
| | COMPLYING WITH 206.4. |
| | |
| | 1B) 2ND REQUEST, SHOW THE ELEVATIONS AT THE CORNERS OF |
| | THE ACCESSIBLE PARKING SPACE AND ACCESS AISLE ( SHOW |
| | ELEVATION MARKERS) TO SEE IF THEY COMPLY WITH THE 2020 |
| | ACCESSIBILITY CODE SECTION 502.4 ACCESS AISLE & PARKING |
| | SPACE SAME LEVEL/ 502.4, FLOOR AND GROUND SURFACES. |
| | PARKING SPACES AND THE ACCESS AISLES SERVING THEM SHALL |
| | COMPLY WITH 302. ACCESS AISLES SHALL BE AT THE SAME |
| | LEVEL AS THE PARKING SPACES THEY SERVE. |
| | CHANGES IN LEVEL ARE NOT PERMITTED. EXCEPTION: SLOPES |
| | NOT GREATER THAN 1:48 SHALL BE PERMITTED. |
| | |
| | 1C) 2ND REQUEST SHOW ELEVATIONS WITH ELEVATION MARKERS. |
| | THERE IS NO DETAIL OF THE TRANSITION FROM THE SIDEWALK |
| | TO THE ACCESS AISLE SHOWING A DROPPED CURB. |
| | 2020 FBC-ACCESSIBILITY CODE SECTION 406.5. LOCATION. |
| | CURB RAMPS AND THE FLARED SIDES OF THE CURB RAMPS SHALL |
| | NOT BE LOCATED SO THAT THEY DO NOT PROJECT INTO |
| | VEHICULAR TRAFFIC LANES, PARKING SPACES, OR PARKING |
| | ACCESS AISLES. CURB RAMPS AT MARKED CROSSINGS SHALL BE |
| | WHOLLY CONTAINS WITHIN THE MARKINGS, EXCLUDING FLARED |
| | SIDES. ALSO SEE FIGURE 406.4. LANDINGS AT THE TOP OF |
| | CURB RAMPS. |
| | |
| | 1D) 2ND REQUEST. PLEASE SHOW HOW A CRUSHED AND |
| | COMPACTED SURFACE MEETS THE REQUIREMENTS OF 302 AND THE |
| | ADVISORY. THE ONLY TIME THIS HAS BEEN ALLOWED IS FOR |
| | TEMPORARY CONSTRUCTION TRAILERS. |
| | 2020 FBC-ACCESSIBILITY CODE, ACCESSIBLE PARKING SPACES |
| | MUST MEET THE REQUIREMENTS OF 302.1 GROUND AND FLOOR |
| | SURFACES SHALL BE STABLE, FIRM, AND SLIP RESISTANT AND |
| | SHALL COMPLY WITH 302. |
| | ADVISORY 302.1. A STABLE SURFACE IS ONE THAT REMAINS |
| | UNCHANGED BY CONTAMINANTS OR APPLIED FORCES SO THAT |
| | WHEN THE CONTAMINANT OR FORCE IS REMOVED, THE SURFACE |
| | RETURNS TO ITS ORIGINAL CONDITION. |
| | |
| | 1E) COMPLIED. |
| | |
| | 2) THE LIFE SAFETY SHEET LS1: |
| | 2A) SEMI-COMPLIED. SHEET LS1 & A8. THE REVISION NOW |
| | SHOWS COMPLIANCE FOR WHEELCHAIR ENTRY WITH SEAT BUT THE |
| | WATERCLOSET DOES NOT SHOW COMPLIANCE WITH THE REQUIRED |
| | SIDE GRAB BAR ACCESS. CODE 604.5.1. |
| | |
| | OLD 2ND ROUND COMMENTS. THE LS1 SHEET AND A8 SHOW A |
| | UNISEX ACCESSIBLE BATHROOM (SHOWER). THE SHOWER IS |
| | DEPICTED AS A 3X3 FOOT MODULAR PAN SHOWER. ON THE RIGHT |
| | SIDE OF THE SHOWER ENTRY IS AN EXTERIOR WALL. ON THE |
| | LEFT SIDE OF THE SHOWER THERE IS A WALL THAT PROJECTS |
| | OUT PAST THE SHOWER APPROXIMATELY 1 FOOT. THE 3 X3 FOOT |
| | SHOWER IS CONSIDERED A TRANSFER TYPE SHOWER SEE 608.2.1 |
| | ACCESSIBILITY CODE AND REQUIRES AN ADDITIONAL ONE-FOOT |
| | CLEARANCE BEYOND THE SHOWER OPENING TO BE ABLE TO |
| | TRANSFER FROM A WHEELCHAIR WHEN PARALLEL WITH THE FRONT |
| | OF THE SHOWER. SEE FIGURE 608.2.1. |
| | 2B) 2ND REQUEST. PLEASE REVIEW SHEET A8 DRINKING |
| | FOUNTAIN ELEVATION VIEWS. YES YOU MEET THE 27 MAX |
| | HEIGHT FOR THE LOWER DRINKING FOUNTAIN BUT NOT THE |
| | UPPER DRINKING FOUNTAIN AS DEPICTED SOME SORT OF |
| | BARRIER NEEDS TO BE PLACED FOR A BLIND PERSON WITH |
| | WALKING CANE IF WALKING TOWARDS THE UPPER DRINKING |
| | FOUNTAIN TO SHOW COMPLIANCE, SOME MANUFACTURES MAKE A |
| | SKIRT THAT CAN BE APPLIED TO THE UPPER FOUNTAIN FOR |
| | COMPLIANCE A OPTION. |
| | ORIGINAL COMMENT. THE LS1 SHEET AND A8 SHOW HIGH/ LOW |
| | DRINKING FOUNTAINS. DETAILS ON SHEET A8 SHOW A SIDE |
| | VIEW OF THE LOW SIDE DRINKING FOUNTAIN AT A HEIGHT OF 2 |
| | FEET 3 INCHES FROM THE FLOOR LEVEL TO THE BOTTOM OF THE |
| | DRINKING FOUNTAIN IN COMPLIANCE WITH THE 2020 |
| | ACCESSIBILITY CODE SECTION 307.2 PROTRUSION LIMITS. THE |
| | LEFT-HAND SIDE DRINKING FOUNTAIN MEETS THE REQUIREMENTS |
| | FOR STANDING OCCUPANTS BUT DOES NOT AS DEPICTED MEET |
| | THE PROTRUSION LIMITS, THE BOTTOM OF THE DRINKING |
| | FOUNTAIN IS HIGHER THAN 27 INCHES FROM THE FLOOR. |
| | |
| | 2C-D) COMPLIED. |
| | |
| | 3) 2ND REQUEST. SHEET A6.0: |
| | 3A) 2ND REQUEST, NOT ADDRESSED. IF YOU CLASSIFY THE |
| | BUILDING AS A IIB THEN ALL FRAMING MEMBERS AND ROOF |
| | DECKING NEED TO BE IDENTIFIED TO MEET THAT DEFINITION |
| | FOUND UNDER TABLE 601 AND 603.1 OTHERWISE THE BUILDING |
| | SHOULD BE LABELED IIIB. |
| | ORIGINAL COMMENT. PLEASE NOTE THE COVERSHEET LIST THIS |
| | CONSTRUCTION TYPE AS IIB NON-SPRINKLERED BUILDING. THE |
| | BUILDING SECTIONS ON SHEET A6.0 DO NOT INDICATE IF THE |
| | TRUSSED ARCH IS STEEL OR LAMINATED WOOD? THE SECTION |
| | ALSO FAILED TO DEFINE THE ROOF FRAMING MEMBERS/ PURLINS |
| | AND THE ROOF SHEATHING MATERIAL? ADDITIONAL INFORMATION |
| | IS REQUIRED. 2020 FBC-BUILDING CODE 603.1 .1.3 ROOF |
| | CONSTRUCTION, INCLUDING GIRDERS, TRUSSES FRAMING AND |
| | DECKING. ALL MUST BE FIRE RETARDANT TREATED WOOD. |
| | |
| | 3B) 2ND REQUEST, NOT ADDRESSED. PLEASE ADD RESPONSE |
| | NOTES TO PLAN INDICATING FLOOR LOADING. EVERY PERMIT |
| | STANDS ALONE FOR INFORMATION. |
| | 2020 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| | CODE, CHAPTER 1, ADMINISTRATION 107.2.1. CONSTRUCTION |
| | DOCUMENTS SHALL BE SUFFICIENT CLARITY TO INDICATE THE |
| | LOCATION, NATURE AND EXTENT OF THE WORK PROPOSED AND |
| | SHOW IN DETAIL THAT IT WILL CONFORM TO THE PROVISIONS |
| | OF THIS CODE AND RELEVANT LAWS, ORDINANCES, RULES AND |
| | REGULATIONS, AS DETERMINED BY THE BUILDING OFFICIAL. |
| | SECTION 2 & 3 BOTH SHOW A EXISTING CRAWL SPACE THE PLAN |
| | DOES NOT SHOW HOW THE ADDITIONAL GRAVITY LOADS PLUS |
| | STORAGE LOADS FROM THE NEW ATTIC SPACE ARE GOING TO BE |
| | TRANSFERRED TO THE FLOOR WITHOUT NEW COLUMNS OR PIERS |
| | BENEATH THE FIRST FLOOR LEVEL. 107.2. 1.. 2020 WEST |
| | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| | CHAPTER 1, ADMINISTRATION 107.2.1. DRAWINGS & |
| | SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM |
| | OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS, |
| | WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE |
| | TECHNICAL CODES. SUCH INFORMATION SHALL BE SPECIFIC TO |
| | THE TECHNICAL CODES. CONSTRUCTION DOCUMENTS SHALL BE |
| | SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND |
| | EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT |
| | WILL CONFORM TO THE PROVISIONS OF THIS CODE AND |
| | RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS |
| | DETERMINED BY THE BUILDING OFFICIAL. |
| | |
| | 3C) 2ND REQUEST, NOT ADDRESSED. SORRY IT WAS ASSUMED |
| | THE MEZZANINE LEVEL (ATTIC) TO BE STORAGE. THE LS1 |
| | SHEET NOR PROPOSED FLOOR PLAN SHOW A OCCUPANCY TYPE OR |
| | OCCUPANT LOAD. WITH THE 42 INCH HIGH RAIL WALL IT MEETS |
| | THE DEFINITION OF MEZZANINE, ASSUMED STORAGE SINCE |
| | THERE IS NO PERMANENT STAIR NOR IS THERE VERTICAL |
| | ACCESSIBILITY FOR OCCUPANT LOAD MORE THAN 5. SEE 2020 |
| | FBC-ACCESSIBILITY 201.1.1 EXCEPTION 3 . |
| | ORIGINAL COMMENT. THE BUILDING SECTIONS SHOWN ON THIS |
| | SHEET DO NOT INDICATE WHAT TYPE OF LIVE LOADS ARE GOING |
| | TO BE PRODUCED BY STORAGE IN THE ATTIC. TABLE 1607.1 |
| | STORAGE LIGHT IS 125 PSF, HEAVY AT 250 PSF |
| | |
| | 3D) 2ND REQUEST, NOT ADDRESSED. 2020 FBC-BUILDING CODE |
| | SECTION 1603.1. THE DESIGN LOADS AND OTHER INFORMATION |
| | PERTINENT TO THE STRUCTURAL DESIGN SHALL BE INDICATED |
| | ON THE CONSTRUCTION DOCUMENTS. |
| | |
| | 4) SHEET A8; |
| | 4A-C) COMPLIED. |
| | |
| | 4D) 2ND REQUEST.PLEASE PROVIDE SPECS FOR THE RAINBOW |
| | ATTIC STAIRS. 107.2.1 2020 WEST PALM BEACH AMENDMENTS |
| | TO THE FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATION |
| | 107.2.1. DRAWINGS & SPECIFICATIONS SHALL CONTAIN |
| | INFORMATION, IN THE FORM OF NOTES OR OTHERWISE, AS TO |
| | THE QUALITY OF MATERIALS, WHERE QUALITY IS ESSENTIAL TO |
| | CONFORMITY WITH THE TECHNICAL CODES. SUCH INFORMATION |
| | SHALL BE SPECIFIC TO THE TECHNICAL CODES. |
| | |
| | 5) A TRANSMITTAL LETTER / NARRATIVE LISTING THE |
| | ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF |
| | THE REVISION MADE, IDENTIFYING THE SHEET OR |
| | SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL |
| | HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR |
| | ANTICIPATED COOPERATION. |
| | |
| | PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS |
| | REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT |
| | REVIEW CYCLE. |
| | |
| | |
| | MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM |
| | PART-TIME/ SEMI-RETIRED. |
| | |
| | IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET |
| | BACK INTO THE OFFICE CALL |
| | (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL. |
| | THANK YOU. |
| | |
| | JAMES A. WITMER BN, PX, SFP, CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES |
| | DEPARTMENT |
| | 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 |
| | TEL: 561-805-6717 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |