| Date |
Text |
| 2022-05-23 13:23:06 | 2ND REVIEW FBC-2020 PLUMBING |
| | PERMIT- 22021250 |
| | 3/7/2022 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| | 2020 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. FAILED COMMENTS FROM THE |
| | 1ST REVIEW ARE LISTED BELOW WITH ADDITIONAL NOTES. |
| | |
| | 1) FAILED. SHEET LS1 & P3: PROVIDE PLUMBING FIXTURE |
| | CALCULATIONS IN ACCORDANCE WITH TABLE 403.1 FBC P. |
| | PLEASE NOTE THAT DRINKING FOUNTAINS AND SERVICE SINKS |
| | ARE REQUIRED FIXTURES FOR BUSINESS OCCUPANCIES. PLEASE |
| | REVISE THE PLANS ACCORDINGLY TO SHOW THE LOCATIONS OF |
| | THE FIXTURES, PLUMBING PIPING AND ACCESSIBILITY |
| | DETAILS- SEC. 107.2.1 WPB. FIXTURE CALCULATIONS NOT |
| | PROVIDED. |
| | |
| | 3) FAILED. A1 & A8: MISSING ACCESSIBILITY DETAILS- FBC |
| | ACC: THE CORRECTED PLANS STILL HAVE SOME MISSING |
| | DETAILS. |
| | |
| | B) FAILED. CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR |
| | THE LAVATORIES- SEC. 606.2. A 48-INCH DEPTH DIMENSION |
| | IS REQUIRED. THE PLAN SHOWS 3'0". |
| | E) FAILED. HEIGHT OF THE MIRROR FROM THE FINISHED FLOOR |
| | TO THE REFLECTIVE SURFACE- SEC. 603.3. THE DETAIL SHOWS |
| | THE MEASUREMENT TO THE FRAME. DIMENSION NOT SHOWN TO |
| | THE REFLECTIVE SURFACE. |
| | F) FAILED. LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF |
| | GRAB BARS FOR THE WATER CLOSETS- SECS. 604.5 & 609.4, |
| | FIGURES 604.5.1 & 604.5.2. THE DETAILS SHOW THE |
| | MEASUREMENTS TO THE CENTERS OF THE BARS AND NOT TO THE |
| | TOPS OF THE GRIPPING SURFACES. REAR WATER CLOSET GRAB |
| | BAR DIMENSIONS NOT SHOWN. |
| | H) FAILED. CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR |
| | THE SHOWER- SECTION 608.2.1 REQUIRED CLEAR FLOOR SPACE |
| | SHALL BE 30X48-INCHES IN A PARALLEL POSITIONED MEASURED |
| | FROM THE CONTROL SIDE OF THE SHOWER. THE DRAWING SHOWS |
| | THERE IS NOT ADEQUATE SPACE TO PROVIDED TO MEET |
| | COMPLIANCE. |
| | I) FAILED. LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF |
| | GRAB BARS FOR THE ACCESSIBLE SHOWER- SECTION 608.3 AND |
| | 608.3.1 NOT PROVIDED. |
| | J) FAILED. LOCATION OF CONTROL, FAUCET, AND SHOWER |
| | SPRAY IN THE SHOWER- SECTION 608.5.1. NOT PROVIDED. |
| | L) FAILED. LOCATION OF ACCESSIBLE SHOWER SEAT- SECTIONS |
| | 610.3 & 610.3.2. NOT PROVIDED. |
| | M) FAILED. DRINKING FOUNTAINS: REFER TO SECS. 306, 307, |
| | AND 602 AND PROVIDE DRINKING FOUNTAIN INSTALLATION |
| | DETAILS AND ELEVATION VIEWS SHOWING KNEE AND TOE |
| | CLEARANCES, SPOUT HEIGHTS, AND SPOUT LOCATIONS. SHOW |
| | THE REQUIRED 30 X 48 IN. CLEAR FLOOR SPACE FOR A |
| | FORWARD WHEELCHAIR APPROACH TO THE FOUNTAIN- SEC. |
| | 602.2. SHOW THE LOCATIONS OF THE FOUNTAINS WILL BE IN |
| | COMPLIANCE WITH SECTION 307.2 PROTRUSION LIMITS. THE |
| | DRAWINGS SHOW THE DRINKING FOUNTAINS WILL BE PROTRUDING |
| | INTO THE CIRCULATION PATH BEYOND THE MAXIMUM 4-INCHES |
| | ALLOWED- SEC. 307.2 FBC ACC. WING WALLS ON EACH SIDE OF |
| | THE FOUNTAIN CAN BE INSTALLED OR BARRIER-FREE TYPE |
| | FOUNTAINS. |
| | |
| | NEW COMMENT: |
| | |
| | 1) SHEET A8: SHOW THE CENTERLINE OF THE TOILET PAPER |
| | DISPENSER MEASURED FROM THE FRONT OF THE WATER CLOSETS |
| | SEC. AND FIGURE 604.7 FBC ACC. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |