| 2022-03-07 14:17:06 | 1ST REVIEW FBC-2020 PLUMBING |
| | PERMIT- 22021250 |
| | 3/7/2022 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| | 2020 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET LS1 & P3: PROVIDE PLUMBING FIXTURE |
| | CALCULATIONS IN ACCORDANCE WITH TABLE 403.1 FBC P. |
| | PLEASE NOTE THAT DRINKING FOUNTAINS AND SERVICE SINKS |
| | ARE REQUIRED FIXTURES FOR BUSINESS OCCUPANCIES. PLEASE |
| | REVISE THE PLANS ACCORDINGLY TO SHOW THE LOCATIONS OF |
| | THE FIXTURES, PLUMBING PIPING AND ACCESSIBILITY |
| | DETAILS- SEC. 107.2.1 WPB. |
| | |
| | 2) LS1, P1: LABEL THE TOILET ROOMS AS EITHER MALE, |
| | FEMALE OR UNISEX- SECS. 403.2 & 403.2.1 FBC P. PLEASE |
| | NOTE THAT SIGNAGE IS REQUIRED- SEC. 403.4. |
| | |
| | 3) A1 & A8: MISSING ACCESSIBILITY DETAILS- FBC ACC: |
| | A) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE |
| | WATER CLOSETS- SEC. 604.3. |
| | B) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE |
| | LAVATORIES- SEC. 606.2. |
| | C) TURNING SPACE DIAMETERS- SEC. 304.3. |
| | D) HEIGHTS OF THE WATER CLOSET SEATS FROM THE FINISHED |
| | FLOORS- SEC. 604.4. THE DETAILS SHOW THE MEASUREMENTS |
| | TO THE RIM AND NOT THE SEAT. |
| | E) HEIGHT OF THE MIRROR FROM THE FINISHED FLOOR TO THE |
| | REFLECTIVE SURFACE- SEC. 603.3. THE DETAILS SHOWS THE |
| | MEASUREMENT TO THE FRAME. |
| | F) LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF GRAB |
| | BARS FOR THE WATER CLOSETS- SECS. 604.5 & 609.4, |
| | FIGURES 604.5.1 & 604.5.2. THE DETAILS SHOW THE |
| | MEASUREMENTS TO THE CENTERS OF THE BARS AND NOT TO THE |
| | TOPS OF THE GRIPPING SURFACES. |
| | G) INTERIOR DIMENSIONS OF THE SHOWER- SEC. 608.2.1. |
| | H) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE |
| | SHOWER- SECTION 608.2.1 |
| | I) LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF GRAB |
| | BARS FOR THE ACCESSIBLE SHOWER- SECTION 608.3 AND |
| | 608.3.1 |
| | J) LOCATION OF CONTROL, FAUCET, AND SHOWER SPRAY IN THE |
| | SHOWER- SECTION 608.5.1. |
| | K) SHOWER SPRAY UNIT SPECIFICATIONS INCLUDING ON/OFF |
| | CONTROL AND NON-POSITIVE SHUTOFF PER SECTION 608.6. |
| | L) LOCATION OF ACCESSIBLE SHOWER SEAT- SECTIONS 610.3 & |
| | 610.3.2. |
| | M) DRINKING FOUNTAINS: REFER TO SECS. 306, 307, AND 602 |
| | AND PROVIDE DRINKING FOUNTAIN INSTALLATION DETAILS AND |
| | ELEVATION VIEWS SHOWING KNEE AND TOE CLEARANCES, SPOUT |
| | HEIGHTS, AND SPOUT LOCATIONS. SHOW THE REQUIRED 30 X 48 |
| | IN. CLEAR FLOOR SPACE FOR A FORWARD WHEELCHAIR APPROACH |
| | TO THE FOUNTAIN- SEC. 602.2. SHOW THE LOCATIONS OF THE |
| | FOUNTAINS WILL BE IN COMPLIANCE WITH SECTION 307.2 |
| | PROTRUSION LIMITS. |
| | |
| | 4) S1 & P1: PROVIDE A SLAB REPAIR DETAIL- SEC. 107.2.1 |
| | WPB. |
| | |
| | 5) P3: PROVIDE A SHOWER PAN DETAIL- 421.5.2 FBC P. |
| | |
| | 6) P3: PROVIDE SHOWER VALVE AND SPRAY PLUMBING |
| | SPECIFICATIONS- 412.2 & 412.3 FBC P. |
| | |
| | 7) P3: SHOW THE LOCATION OF THE WATER HEATER EXPANSION |
| | TANK- SEC. 607.3 FBC P. |
| | |
| | 8) P2 & P3: SHOW THE WATER HEATER PAN DRAIN PIPING RUN |
| | AND DISCHARGE LOCATION- SEC. 504.7.1 FBC P. |
| | |
| | 9) P2 & P3: INDICATE HOW TEMPERED WATER WILL BE |
| | DELIVERED FROM THE LAVATORIES- SEC. 419.5 FBC P. PLEASE |
| | NOTE THAT TEMPERED WATER MIXING VALVES SHALL CONFORM TO |
| | ASSE 1070. |
| | |
| | 10) P3: PROVIDE SHOWER FLOOR AND WALL FINISH DETAILS- |
| | SEC. 421.4.1. |
| | |
| | 11) A8: REFER TO SECTION 310.3 FBC P AND SEC.1210.2.2 |
| | FBC B WALLS AND PARTITIONS. |
| | WALLS AND PARTITIONS WITHIN 2 FEET OF SERVICE SINKS, |
| | URINALS AND WATER CLOSETS SHALL HAVE A SMOOTH, HARD, |
| | NONABSORBENT SURFACE, TO A HEIGHT OF NOT LESS THAN 4 |
| | FEET ABOVE THE FLOOR, AND EXCEPT FOR STRUCTURAL |
| | ELEMENTS, THE MATERIALS USED IN SUCH WALLS SHALL BE OF |
| | A TYPE THAT IS NOT ADVERSELY AFFECTED BY MOISTURE. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL/PLUMBING PLANS EXAMINER |