| 2022-03-02 10:42:32 | JONATHAN BROOKS JR. |
| | BUILDING PLANS EXAMINER |
| | WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM |
| | PHONE (561) 805-6656 |
| | EMAIL: [email protected] |
| | |
| | 1ST REVIEW: FBC 2020 7TH EDITION |
| | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) |
| | FBC B = FBC BUILDING |
| | FBC R = FBC RESIDENTIAL |
| | FBC EB = FBC EXISTING BUILDING |
| | FBC A = FBC ACCESSIBILITY |
| | FBC EC = FBC ENERGY CONSERVATION |
| | WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC |
| | RESULTS: DENIED |
| | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| | TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT |
| | CITY HALL, OR EMAIL [email protected]. |
| | |
| | 1. PROVIDE A COMPLETE SET OF 2020 CODE VERSION PRODUCT |
| | APPROVALS/NOA'S FOR THE PROPOSED DOME ROOF RECOVER |
| | SYSTEM TO BE USED. SUBMITTED PRODUCT APPROVAL |
| | FL2533-R26 TABLE 7A SYSTEM TYPE A-1 R-52 IS FOR |
| | STRUCTURAL CONCRETE DECKS. ALL APPLICABLE DETAILS AND |
| | ATTACHMENTS MUST BE CLEARLY IDENTIFIED ON THE PRODUCT |
| | APPROVAL DRAWINGS. DETAILS AND ATTACHMENTS NOT |
| | SPECIFICALLY COVERED IN PRODUCT APPROVALS WILL NEED |
| | SITE-SPECIFIC ENGINEERING |
| | 2. FBC EB 706.3(1) PROVIDE A SIGNED AND SEALED MOISTURE |
| | REPORT PREPARED BY A FLORIDA REGISTERED DESIGN |
| | PROFESSIONAL. |
| | 3. PROVIDE FIELD UPLIFT TESTING IN ACCORDANCE WITH |
| | TESTING APPLICATION STANDARD TAS 124 AS REQUIRED BY |
| | NOTE #12 & LIMITATIONS 5.6.3 OF PRODUCT APPROVAL |
| | FL2633-R26 |
| | 4. FBC B 107.2.1 RECOVERING MUST SHOW COMPLIANCE WITH |
| | 706.3 OF THE 2020 FBC-EXISTING BUILDING. |
| | 5. FBC B 1609 PROVIDE A COMPLETE SET OF SIGNED AND |
| | SEALED ENGINEERED DESIGN PRESSURE CALCULATIONS BY A |
| | FLORIDA REGISTERED PROFESSIONAL ENGINEER, REGISTERED |
| | ARCHITECT, OR REGISTERED ROOF CONSULTANT. |
| | 6. FBC B 107.2.1 FOR CLARITY PLEASE PROVIDE A ROOF |
| | DIAGRAM/SKETCH WITH THE AREAS TO RECEIVE NEW ROOFING |
| | CLEARLY IDENTIFIED ON DRAWING; INCLUDE ROOF SLOPE(S), |
| | MEAN ROOF HEIGHT(S). FLAT/LOW SLOPE ROOFS MUST SHOW |
| | POSITIVE DRAINAGE. |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMEMTS. |
| | |