| 2022-02-25 15:47:08 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | 1) THERE IS AN INDICATION OF THE SCOPE OF WORK OF |
| | REPLACING THE TILE AND THERE IS A SPEC SHEET FOR THE |
| | FLOOR UNDERLAYMENT, BUT NO PRODUCT NAME NOR A PRODUCT |
| | SPEC SHEET FOR THE ACTUAL PROPOSED TILE. |
| | |
| | FLOORING IS MANUFACTURED AROUND THE WORLD AND TILE CAN |
| | HAVE DIFFERENT MEANING A PRODUCED DIFFERENTLY AND NOT |
| | ALL ARE TESTED AND MEETING LISTED AND NFPA STANDARDS. |
| | |
| | 30.3.3.3 INTERIOR FLOOR FINISH. |
| | 30.3.3.1 GENERAL. INTERIOR FINISH SHALL BE IN |
| | ACCORDANCE WITH |
| | SECTION 10.2. |
| | |
| | 10.2.7.2* FLOOR COVERINGS, OTHER THAN CARPET FOR WHICH |
| | 10.2.2.2 |
| | ESTABLISHES REQUIREMENTS FOR FIRE PERFORMANCE, SHALL |
| | HAVE A |
| | MINIMUM CRITICAL RADIANT FLUX OF 0.1 W/CM2. |
| | |
| | FOR THE OFFICIAL RECORD, PLEASE PROVIDE THE PRODUCT |
| | SPEC SHEETS OF THE PROPOSED FINISHED |
| | TILEL FLOORING INDICATING THE FIRE BEHAVIOR RATING. |
| | |
| | *****FYI **** |
| | |
| | PLEASE PROVIDE THE TILE TYPE I.E. CERAMIC, MARBLE, |
| | TERRACOTTA, STONE WHICH WOULD NOT REQUIRE A SPEC SHEET. |
| | |
| | FOR OTHER TYPE OF TILE PRODUCT TYPE I.E. VINYL OR VINYL |
| | PLANKS, CORK, WOOD PLEASE PROVIDE THE MANUFACTURE |
| | PRODUCT FLAME SPREAD/PRODUCT SAFETY TEST SHEET |
| | |
| | |
| | |
| | 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |