| Plan Review Notes For Permit 22021223 |
| Permit Number |
22021223 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2022-03-01 08:07:13 | 1ST REVIEW FBC-2020 PLUMBING | | | PERMIT- 22021223 | | | 3/1/2022 | | | | | | CODES IN EFFECT: | | | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 | | | FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 | | | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION | | | 2020 | | | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) SHEET A1.1: REFER TO SECTION 1004.8 FBC B | | | CONCENTRATED BUSINESS AREAS. IT APPEARS THE OCCUPANT | | | LOAD CALCULATIONS ARE INCORRECT FOR THE CONCENTRATED | | | BUSINESS AREAS AND ROOMS WHICH SHALL BE CALCULATED BY | | | THE ACTUAL LOAD (CUBICLES, SEATING) BUT NOT LESS TAN | | | ONE OCCUPANT PER 50 SQUARE FEET OF GROSS OCCUPIABLE | | | FLOOR SPACE. THE INCREASED LOAD MAY RESULT IN | | | ADDITIONAL PLUMBING FIXTURE REQUIREMENTS BASED ON SEC. | | | 810.1 FBC EX AND TABLE 403.1 FBC P. PLEASE PROVIDE | | | FIXTURE CALCULATIONS BASED ON THE INCREASED TOTAL | | | OCCUPANT LOAD. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL/PLUMBING PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|