Plan Review Notes
Plan Review Notes For Permit 22021203
Permit Number 22021203
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2022-02-28 14:06:08UNDERGROUND LINE PLAN ON SHEET C2.3 CIVIL.
  
 HYDROSTATIC TESTS. ALL PIPING AND ATTACHED
 APPURTENANCES SUBJECTED TO SYSTEM WORKING PRESSURE
 SHALL BE HYDROSTATICALLY TESTED AT 200 PSI (13.8 BAR)
 AND SHALL MAINTAIN THAT PRESSURE WITHOUT LOSS FOR 2
 HOURS PER NFPA 24.
  
 PER CITY CODES, ALL WORK IS SUBJECT TO FIELD
 INSPECTIONS AND APPROVAL.
  
 LT. BRIAN DOLAN
 DIVISION OF FIRE PREVENTION
 561-804-4752
 [email protected]