Plan Review Notes
Plan Review Notes For Permit 22021191
Permit Number 22021191
Review Stop B
Sequence Number 1
Notes
Date Text
2022-03-21 11:57:12WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 22021191
 ADD: 1601 BELVEDERE RD. # 401-E
 CONT: R & M LOGISTICS, CORP.
 TEL: 305-747-4686
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MON. MARCH 21ST/ 2022
 ACTION: DENIED
  
 1) SHEET A5- LIFE SAFETY PLAN SHOW A BREAK ROOM # 410
 BUT THERE ARE NO ELEVATION VIEWS TO SHOW COMPLIANCE
 WITH THE 2020 FBC-ACCESSIBILITY CODE SECTIONS:
  
 1A) 606 LAVATORIES AND SINKS> 2020 FBC-ACCESSIBILITY
 CODE SECTION 606.3 HEIGHT. LAVATORIES AND SINKS SHALL
 BE INSTALLED WITH THE FRONT OF THE HIGHER OF THE RIM OR
 COUNTER SURFACE 34 INCHES MAXIMUM ABOVE THE FINISH
 FLOOR OR GROUND.
  
 1B) 606.2 CLEAR FLOOR SPACE. A CLEAR FLOOR SPACE
 COMPLYING WITH 305, POSITIONED FOR A FORWARD APPROACH,
 AND KNEE AND TOE CLEARANCE COMPLYING WITH 306 SHALL BE
 PROVIDED, SEE EXCEPTIONS ALSO, BUT SHOW THE REQUIRED
 CLEAR FLOOR SPACE ON THE FLOOR PLAN.
  
 1C) 606.5 EXPOSED PIPES AND SURFACES. WATER SUPPLY &
 DRAINPIPES UNDER LAVATORIES AND SINKS SHALL BE
 INSULATED OR OTHERWISE CONFIGURED TO PROTECT AGAINST
 CONTACT.
  
 1D) 902.3 HEIGHT. THE TOPS OF WORK SURFACES SHALL BE 28
 INCHES MINIMUM AND 34 INCHES MAXIMUM ABOVE THE FINISH
 FLOOR OR GROUND.
  
 2) A TRANSMITTAL LETTER / NARRATIVE LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
  
 MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM
 PART-TIME/ SEMI-RETIRED.
  
 IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET
 BACK INTO THE OFFICE CALL
 (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL.
 THANK YOU.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved