| Plan Review Notes For Permit 22021141 |
| Permit Number |
22021141 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2022-03-10 15:41:30 | 1ST REVIEW FBC-2020 MECHANICAL | | | PERMIT-22021141 | | | | | | CODES IN EFFECT: | | | | | | FBC B- FLORIDA BUILDING CODE | | | FBC M- FLORIDA MECHANICAL CODE | | | FBC EC- FLORIDA ENERGY CONSERVATION | | | FBC FG- FLORIDA FUEL GAS | | | FBC EX- FLORIDA EXISTING BUILDING CODE | | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) PLEASE REMOVE THE RETURN AIR DUCT AND GRILLE FROM | | | THE CLOSET BEHIND THE COPY ROOM. FBC M 601.5: 7 | | | | | | 2) PLEASE PROVIDE THE OUTDOOR AIR CALCULATIONS FOR EACH | | | USE OF SPACE BASED ON FBC M 403.3.1.1. THIS CODE | | | SECTION TELLS US WE USE TABLE 403.3.1.1 TO CALCULATE | | | THE OCCUPANT DENSITY AND NOT USE THE ARCHITECTURAL | | | EGRESS OCCUPANT COUNT. THE RECEPTION AND CONFERENCE | | | ROOM AREAS HAVE LOW OUTDOOR AIR CALCULATIONS BASED ON | | | THE CODE SECTIONS. | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|