| Plan Review Notes For Permit 22021089 |
| Permit Number |
22021089 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2022-03-04 10:06:24 | 1ST REVIEW FBC-2020 MECHANICAL | | | PERMIT-22021089 | | | | | | CODES IN EFFECT: | | | | | | FBC B- FLORIDA BUILDING CODE | | | FBC M- FLORIDA MECHANICAL CODE | | | FBC EC- FLORIDA ENERGY CONSERVATION | | | FBC FG- FLORIDA FUEL GAS | | | FBC EX- FLORIDA EXISTING BUILDING CODE | | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) THE SUBMITTED PLAN REVIEW REQUEST FORM DID NOT | | | INCLUDE THE DESCRIPTION OF INFORMATION. PLEASE ADD THE | | | SCOPE OF WORK FOR THIS REVISION. | | | | | | 2) THE ENERGY CALCULATIONS AND THE MECHANICAL EQUIPMENT | | | SIZING CALCULATIONS WERE SUBMITTED BUT THE MECHANICAL | | | DRAWINGS WITH THE MINI-SPLIT INFORMATION WAS NOT | | | SUBMITTED. PLEASE SUBMIT THE MATERIAL NEED TO REVIEW | | | THIS PROJECT. | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|