| Plan Review Notes For Permit 22021073 |
| Permit Number |
22021073 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2022-03-07 09:47:20 | 2ND PLUMBING REVIEW | | | | | | V7 FBC P - 2020 FLORIDA PLUMBING CODE | | | | | | THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED | | | BY RYAN BROWN WITH THE FOLLOWING COMMENTS. | | | | | | V7 FBC P -- 307.3 -- THE FIRE STOPPING DETAILS YOU HAVE | | | PROVIDED STATE IN THE USE FOR 2" AND SMALLER PVC. THESE | | | PENETRATIONS ARE FOR 3" PVC. PLEASE SUBMIT FIRE | | | STOPPING DETAILS THAT ARE SPECIFIC TO THE PENTRANT AND | | | TO THE CONSTRUCTION TYPE. | | | | | | | | | RYAN W. BROWN | | | CHIEF PLUMBING INSPECTOR | | | OFFICE: 561-805-6692 | | | CELL: 561-517-4293 | | | EMAIL: [email protected] | | | |
|