Plan Review Notes
Plan Review Notes For Permit 22021073
Permit Number 22021073
Review Stop P
Sequence Number 2
Notes
Date Text
2022-03-07 09:47:202ND PLUMBING REVIEW
  
 V7 FBC P - 2020 FLORIDA PLUMBING CODE
  
 THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED
 BY RYAN BROWN WITH THE FOLLOWING COMMENTS.
  
 V7 FBC P -- 307.3 -- THE FIRE STOPPING DETAILS YOU HAVE
 PROVIDED STATE IN THE USE FOR 2" AND SMALLER PVC. THESE
 PENETRATIONS ARE FOR 3" PVC. PLEASE SUBMIT FIRE
 STOPPING DETAILS THAT ARE SPECIFIC TO THE PENTRANT AND
 TO THE CONSTRUCTION TYPE.
  
  
 RYAN W. BROWN
 CHIEF PLUMBING INSPECTOR