Plan Review Notes
Plan Review Notes For Permit 22021073
Permit Number 22021073
Review Stop B
Sequence Number 1
Notes
Date Text
2022-05-10 14:22:23PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SEVENTH EDITION (2020)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE PROPOSED WORK INCLUDES BORING HOLES THROUGH
 EXISTING FLOOR SLABS IN A THRESHOLD BUILDING (MORE THAN
 3 STORIES IN HEIGHT) WHICH IS STRUCTURAL WORK. THIS
 PROJECT REQUIRES A STATE OF FLORIDA LICENSED GENERAL
 CONTRACTOR (CGC) TO PULL A BUILDING PERMIT FOR THE
 STRUCTURAL WORK. THE PENETRATION FIRESTOP SYSTEM FOR
 THE FIRE-RESISTANCE RATED FLOOR ASSEMBLIES SHOULD ALSO
 BE INCLUDED IN THE WORK OF THE GC. FS 489 & FS 553.71
  
 2) A THRESHOLD BUILDING SPECIAL INSPECTOR WILL BE
 REQUIRED TO PERFORM THE STRUCTURAL INSPECTIONS FOR THIS
 PROJECT. SUBMIT THE REQUIRED THRESHOLD INSPECTION
 DOCUMENTS. FBC AMENDMENTS 110.8.1
  
 3) PROVIDE A FIRESTOP DETAIL WITH A LISTED SYSTEM FOR
 THE FLOOR ASSEMBLY PENETRATIONS. FBC 714.2
2022-03-01 12:40:37CREATED STOP FOR BUILDING TO REVIEW RATED ASSEMBLIES
 FOR NEW PENTETRATIONS MADE BY FLOOR DRAINS.