| Plan Review Notes For Permit 22021072 |
| Permit Number |
22021072 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2022-03-16 13:23:45 | JONATHAN BROOKS JR. | | | BUILDING PLANS EXAMINER | | | WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM | | | PHONE (561) 805-6656 | | | EMAIL: [email protected] | | | | | | 1ST REVIEW: FBC 2020 7TH EDITION | | | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) | | | FBC B = FBC BUILDING | | | FBC R = FBC RESIDENTIAL | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC | | | RESULTS: DENIED | | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT | | | CITY HALL, OR EMAIL [email protected]. | | | | | | 1. FBC R 301 FAC9N-3 SUBMITTED FLORIDA DBPR PRODUCT | | | APPROVAL FL16709-R9 SELECTED OPTION FOR SYSTEM NO W-5; | | | EXPOSURE (B); ENCLOSURE (ENCLOSED); ROOF HEIGHT (H<15) | | | & 15 < H < 20; ULTIMATE WIND SPEED (180) IS NOT | | | CORRECT. THE CORRECT EXPOSURE FOR THE LISTED ADDRESS IS | | | EXPOSURE C, CORRECT WIND SPEED (170). PLEASE SELECT THE | | | CORRECT OPTIONS. | | | 2. FBC B 107.2.1 PROVIDE A ROOF DRAINAGE PLAN THAT | | | COMPLIES WITH SECTION 903.4 OF THE 2020 FBC-RESIDENTIAL | | | AND CHAPTER 11 OF THE 2020 FBC-PLUMBING. SHOW LOCATION | | | & SIZE OF EXISTING AND PROPOSED NEW SCUPPERS. | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMEMTS. | | | |
|