| Plan Review Notes For Permit 22021071 |
| Permit Number |
22021071 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2022-02-25 15:21:58 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | 1) THERE IS NO SITE/BUILDING/FLOOR PLAN INDICATING THE | | | LOCATION(S) OF THE DOOR(S). | | | | | | | | | FOR THE OFFICIAL RECORD, PLEASE PROVIDE THEA | | | SITE/BUILDING/FLOOR PLAN INDICATING THE EXACT | | | LOCATION(S) OF THE DOOR(S) | | | | | | | | | 2) THERE ARE NUMEROUS SPEC SHEETS WITH NUMEROUS DOORS & | | | DOOR PRODUCTS PROVIDED; HOWEVER, THERE ARE NO | | | INDICATIONS OF THE SPECIFIC DOOR OR DOOR PRODUCTS THAT | | | ARE BEING USED. | | | | | | PLEASE HIGHLIGHT THE EXACT DOOR & DOOR PRODUCTS THAT | | | YOU ARE PROPOSING TO USE FROM THE VAROIUS DOOR & DOOR | | | PRODUCT EXAMPLES YOU PROVIDED. | | | | | | | | | 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | | ABOVE. | | | | | | | | | 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | | RE-SUBMITTAL OF THE ABOVE. | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | | | | |
|