| 2022-11-22 09:45:49 | FIRE REVIEW COMMENTS: | | | | | | ADDRESS THE FOLLOWING ON THE PLAN: | | | | | | (1) WHAT IS THE TRAVEL DISTANCE FROM THE MOST REMOTE | | | POINT INSIDE THE WALK- IN COOLER TO AN APPROVED EXIT? | | | | | | (2) WHAT IS THE DOOR LOCKING HARDWARE ON THE WALK-IN | | | COOLER DOOR? | | | | | | (3) NO INDICATION ON THE PLAN TO PROVIDE EMERGENCY | | | LIGHTING OR EXIT SIGNAGE INSIDE THE COOLER. | | | | | | (4) NO MENTION OF FIRE SPRINKLER COVERAGE INSIDE THE | | | WALK-IN COOLER. | | | | | | | | | C. WALKER | | | | | | 561-804-4762 | | | | | | [email protected] | | | |
|