| Plan Review Notes For Permit 22021058 |
| Permit Number |
22021058 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2022-10-18 06:42:58 | PROVIDE INFORMATION ABOUT THE WALK-IN COOLER INCLUDING | | | A COMPLETE DRAWING OF THE REFRIGERATION LINES AND THE | | | LOCATION OF THE CONDENSING UNIT FOR THE WALK-IN COOLER. | | | THE AMOUNT OF REFRIGERATION IN THIS SYSTEM, THE TYPE OF | | | REFRIGERANT. THE ALLOWABLE QUANTITIES OF REFRIGERANT. | | | | | | FMC 1102.1 GENERAL. THE SYSTEM CLASSIFICATION, | | | ALLOWABLE REFRIGERANTS, | | | MAXIMUM QUANTITY, ENCLOSURE REQUIREMENTS, LOCATION | | | LIMITATIONS, AND FIELD PRESSURE TEST REQUIREMENTS SHALL | | | BE | | | DETERMINED AS FOLLOWS: | | | 1. DETERMINE THE REFRIGERATION SYSTEM'S CLASSIFICATION, | | | IN | | | ACCORDANCE WITH SECTION 1103.3. | | | 2. DETERMINE THE REFRIGERANT CLASSIFICATION IN | | | ACCORDANCE | | | WITH SECTION 1103.1. | | | 3. DETERMINE THE MAXIMUM ALLOWABLE QUANTITY OF | | | REFRIGERANT | | | IN ACCORDANCE WITH SECTION 1104, BASED ON TYPE OF | | | REFRIGERANT, SYSTEM CLASSIFICATION AND OCCUPANCY. | | | 4. DETERMINE THE SYSTEM ENCLOSURE REQUIREMENTS IN | | | ACCORDANCE | | | WITH SECTION 1104. | | | 5. REFRIGERATION EQUIPMENT AND APPLIANCE LOCATION AND | | | INSTALLATION SHALL BE SUBJECT TO THE LIMITATIONS OF | | | CHAPTER | | | 3. | | | 6. NONFACTORY-TESTED, FIELD-ERECTED EQUIPMENT AND | | | APPLIANCES | | | SHALL BE PRESSURE TESTED IN ACCORDANCE WITH SECTION | | | 1108. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | | | | | | | | | | | | | |
|