Plan Review Notes
Plan Review Notes For Permit 22021058
Permit Number 22021058
Review Stop M
Sequence Number 1
Notes
Date Text
2022-10-18 06:42:58PROVIDE INFORMATION ABOUT THE WALK-IN COOLER INCLUDING
 A COMPLETE DRAWING OF THE REFRIGERATION LINES AND THE
 LOCATION OF THE CONDENSING UNIT FOR THE WALK-IN COOLER.
 THE AMOUNT OF REFRIGERATION IN THIS SYSTEM, THE TYPE OF
 REFRIGERANT. THE ALLOWABLE QUANTITIES OF REFRIGERANT.
  
 FMC 1102.1 GENERAL. THE SYSTEM CLASSIFICATION,
 ALLOWABLE REFRIGERANTS,
 MAXIMUM QUANTITY, ENCLOSURE REQUIREMENTS, LOCATION
 LIMITATIONS, AND FIELD PRESSURE TEST REQUIREMENTS SHALL
 BE
 DETERMINED AS FOLLOWS:
 1. DETERMINE THE REFRIGERATION SYSTEM'S CLASSIFICATION,
 IN
 ACCORDANCE WITH SECTION 1103.3.
 2. DETERMINE THE REFRIGERANT CLASSIFICATION IN
 ACCORDANCE
 WITH SECTION 1103.1.
 3. DETERMINE THE MAXIMUM ALLOWABLE QUANTITY OF
 REFRIGERANT
 IN ACCORDANCE WITH SECTION 1104, BASED ON TYPE OF
 REFRIGERANT, SYSTEM CLASSIFICATION AND OCCUPANCY.
 4. DETERMINE THE SYSTEM ENCLOSURE REQUIREMENTS IN
 ACCORDANCE
 WITH SECTION 1104.
 5. REFRIGERATION EQUIPMENT AND APPLIANCE LOCATION AND
 INSTALLATION SHALL BE SUBJECT TO THE LIMITATIONS OF
 CHAPTER
 3.
 6. NONFACTORY-TESTED, FIELD-ERECTED EQUIPMENT AND
 APPLIANCES
 SHALL BE PRESSURE TESTED IN ACCORDANCE WITH SECTION
 1108.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  
  
  
  
  