Plan Review Notes
Plan Review Notes For Permit 22021050
Permit Number 22021050
Review Stop M
Sequence Number 2
Notes
Date Text
2022-05-18 08:05:06PLAN REVIEW MECHANICAL
  
 CHRISTOPHER S. THROOP, C.B.O., CFM
 PLANS EXAMINER II PX3169/SFP306
 INSPECTOR BN4338
 BUILDING OFFICIAL BU1635
 ASFPM CERTIFIED FLOODPLAIN MANAGER US-21-11935
 DEVELOPMENT SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 (561) 805-6726
 [email protected]
  
 CODES IN EFFECT:
 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 2017 NEC
  
 2ND REVIEW
  
 COMMENTS FROM 1ST REVIEW HAVE NOT BEEN ADDRESSED. SEE
 BELOW:
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. A MECHANICAL SUB-PERMIT IS REQUIRED.
 PERMITS - 105.1 REQUIRED.
  
 2. PROVIDE AN ENERGY SUBMITTAL.
 SUBMIT AN ENERGY COMPLIANCE REPORT FOR THE ADDITION PER
 FBC EC R101.5.1.1
 R101.5.1.1.1BUILDING THERMAL ENVELOPE ALTERNATIVE.
 AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R402
 SHALL BE SUBMITTED TO THE CODE OFFICIAL TO DEMONSTRATE
 CODE COMPLIANCE BY THIS METHOD. ALTERNATIVELY, A
 FLORIDA RESCHECK COMPUTER PRINTOUT MAY BE SUBMITTED TO
 DEMONSTRATE COMPLIANCE BY SECTIONS R402, R403 AND R404.
  
 3. PROVIDE EQUIPMENT SIZING CALCULATIONS.
 R403.7HEATING AND COOLING EQUIPMENT (MANDATORY).
 FBC E R403.7.1EQUIPMENT SIZING.
 HEATING AND COOLING EQUIPMENT SHALL BE SIZED IN
 ACCORDANCE WITH ACCA MANUAL S BASED ON THE EQUIPMENT
 LOADS CALCULATED IN ACCORDANCE WITH ACCA MANUAL J OR
 OTHER APPROVED HEATING AND COOLING CALCULATION
 METHODOLOGIES, BASED ON BUILDING LOADS FOR THE
 DIRECTIONAL ORIENTATION OF THE BUILDING.
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
  