| Date |
Text |
| 2022-03-21 09:07:00 | PLAN REVIEW MECHANICAL |
| | |
| | CHRISTOPHER S. THROOP, C.B.O., CFM |
| | PLANS EXAMINER II PX3169/SFP306 |
| | INSPECTOR BN4338 |
| | BUILDING OFFICIAL BU1635 |
| | ASFPM CERTIFIED FLOODPLAIN MANAGER US-21-11935 |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | CITY OF WEST PALM BEACH |
| | (561) 805-6726 |
| | [email protected] |
| | |
| | CODES IN EFFECT: |
| | 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST |
| | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| | CHAPTER 1 ADMINISTRATION |
| | 2017 NEC |
| | |
| | 1ST REVIEW |
| | |
| | RESULTS: DENIED |
| | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| | |
| | 1. A MECHANICAL SUB-PERMIT IS REQUIRED. |
| | PERMITS - 105.1 REQUIRED. |
| | |
| | 2. PROVIDE AN ENERGY SUBMITTAL. |
| | SUBMIT AN ENERGY COMPLIANCE REPORT FOR THE ADDITION PER |
| | FBC EC R101.5.1.1 |
| | R101.5.1.1.1BUILDING THERMAL ENVELOPE ALTERNATIVE. |
| | AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R402 |
| | SHALL BE SUBMITTED TO THE CODE OFFICIAL TO DEMONSTRATE |
| | CODE COMPLIANCE BY THIS METHOD. ALTERNATIVELY, A |
| | FLORIDA RESCHECK COMPUTER PRINTOUT MAY BE SUBMITTED TO |
| | DEMONSTRATE COMPLIANCE BY SECTIONS R402, R403 AND R404. |
| | |
| | 3. PROVIDE EQUIPMENT SIZING CALCULATIONS. |
| | R403.7HEATING AND COOLING EQUIPMENT (MANDATORY). |
| | FBC E R403.7.1EQUIPMENT SIZING. |
| | HEATING AND COOLING EQUIPMENT SHALL BE SIZED IN |
| | ACCORDANCE WITH ACCA MANUAL S BASED ON THE EQUIPMENT |
| | LOADS CALCULATED IN ACCORDANCE WITH ACCA MANUAL J OR |
| | OTHER APPROVED HEATING AND COOLING CALCULATION |
| | METHODOLOGIES, BASED ON BUILDING LOADS FOR THE |
| | DIRECTIONAL ORIENTATION OF THE BUILDING. |
| | |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | |
| | |
| | |
| | |