| 2022-05-05 07:52:39 | ELECTRIC REVIEW FAILED |
| | 1) PLEASE LOCATE THE METER BANK AND HOUSE DISCONNECT ON |
| | A SITE PLANS, ONLY A METER IS SHOWN.FBC 107.2 |
| | 2) PLEASE DETAIL ALL CONDUCTOR SIZES, OVERCURRENT |
| | PROTECTION AND WIRING METHODS FOR THE SERVICE AND |
| | FEEDERS TO APARTMENTS. NEC 215.5 |
| | 3) PLEASE DETAIL ELECTRIC LOAD CALCULATION FOR THE |
| | ENTIRE ELECTRIC SERVICE. NEC 215.5 |
| | 4) PLEASE DETAIL SMOKE DETECTORS ON FLOOR PLANS AS |
| | REQUIRED FBC RE 2020, 7TH EDITION |
| | 5) PLEASE DETAIL ALL COMMON WIRING OUTDOOR,HALLWAYS, |
| | INCLUDE WIRING METHODS, CONDUCTOR SIZES AND OVERCURRENT |
| | PROTECTION. FBC 107.2 |
| | 6) VALUE FOR WORK STATED ON PERMIT APPLICATION APPEARS |
| | LOW. PLEASE PROVIDE A BREAKDOWN OF ALL MATERIALS AND |
| | LABOR, OR, AT YOUR DISCRETION, PROVIDE A SIGNED |
| | CONTRACTOR OR PROVIDE A REASONABLE VALUE. WPB F.B.C. |
| | 109.3 |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. |
| | |
| | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE 2020 7TH ED. |
| | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020 |
| | 7TH EDITION |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 |
| | 7TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION |
| | NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |