| Plan Review Notes For Permit 22021046 |
| Permit Number |
22021046 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2022-03-08 13:41:02 | THE EXTENT OF RENOVATION FOR THIS OCCUPANCY WOULD MEET | | | THE THRESHOLD OF EXTENSIVE MODIFICATIONS PER NFPA 101 | | | CHAPTER 43: | | | | | | 43.5.2 EXTENSIVE MODIFICATIONS. | | | 43.5.2.1 THE MODIFICATION OF AN ENTIRE BUILDING OR AN | | | ENTIRE | | | OCCUPANCY WITHIN A BUILDING SHALL BE CONSIDERED AS A | | | RECONSTRUCTION | | | AND SHALL COMPLY WITH THE REQUIREMENTS OF SECTION 43.6 | | | FOR | | | THE APPLICABLE OCCUPANCY, UNLESS OTHERWISE SPECIFIED IN | | | 43.5.2.2. | | | | | | 43.5.2.3 WHERE THE TOTAL AREA OF ALL THE REHABILITATION | | | WORK AREAS | | | INCLUDED IN A MODIFICATION EXCEEDS 50 PERCENT OF THE | | | AREA OF THE | | | BUILDING, THE WORK SHALL BE CONSIDERED AS A | | | RECONSTRUCTION AND | | | SHALL COMPLY WITH THE REQUIREMENTS OF SECTION 43.6 FOR | | | THE APPLICABLE | | | OCCUPANCY, UNLESS OTHERWISE SPECIFIED IN 43.5.2.4. | | | | | | THIS EXTENT OF REHABILITATION (REMODEL) OF THE | | | OCCUPANCY WOULD REQUIRE THE PROPERTY TO ADHERE TO | | | CONDITIONS OF: | | | | | | NFPA 101 CHAPTER 30 NEW APARTMENT BUILDINGS | | | | | | PLEASE PROVIDE DETAILED PLAN FOR MEETING REQUIREMENTS | | | UNDER FLORIDA FIRE PREVENTION CODE. | | | | | | LT. BRIAN DOLAN | | | DIVISION OF FIRE PREVENTION | | | 561-804-4752 | | | [email protected] | | | | | | | | 2022-02-28 08:42:24 | PER CITY CODES, ALL WORK IS SUBJECT TO FIELD | | | INSPECTIONS AND APPROVAL. | | | JOSEPH CLARK | | | OFFICE OF THE FIRE MARSHAL | | | 561-804-4748 | | | [email protected] | | | |
|