Plan Review Notes
Plan Review Notes For Permit 22021045
Permit Number 22021045
Review Stop M
Sequence Number 3
Notes
Date Text
2022-05-06 10:45:541ST REVIEW FMC
 PERMIT: 22021045
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M-103: THE TERMINATION LOCATION FOR THE GREASE
 DUCT DOES NOT MEET THE TERMINATION LOCATIONS OF FMC
 506.3.13.3
 506.3.13.3 TERMINATION LOCATION. EXHAUST OUTLETS SHALL
 BE LOCATED NOT LESS THAN 10 FEET (3048 MM) HORIZONTALLY
 FROM PARTS OF THE SAME OR CONTIGUOUS BUILDINGS,
 ADJACENT BUILDINGS AND ADJACENT PROPERTY LINES AND
 SHALL BE LOCATED NOT LESS THAN 10 FEET (3048 MM) ABOVE
 THE
 ADJOINING GRADE LEVEL. EXHAUST OUTLETS SHALL BE LOCATED
 NOT LESS THAN 10 FEET (3048 MM) HORIZONTALLY FROM OR
 NOT LESS THAN 3 FEET (914 MM) ABOVE AIR INTAKE OPENINGS
 INTO ANY BUILDING.
 EXCEPTION: EXHAUST OUTLETS SHALL TERMINATE NOT LESS
 THAN 5 FEET (1524 MM) HORIZONTALLY FROM PARTS OF THE
 SAME OR CONTIGUOUS BUILDING, AN ADJACENT BUILDING,
 ADJACENT PROPERTY LINE AND AIR INTAKE OPENINGS INTO A
 BUILDING WHERE AIR FROM THE EXHAUST OUTLET DISCHARGES
 AWAY FROM SUCH LOCATIONS.
  
 2) PLEASE EXPLAIN HOW TERMINATING THE GREASE DUCT INTO
 A PARKING LOT WOULD MEET 506.3.13.2 CREATING A PUBLIC
 NUISANCE.
  
 3) IT APPEARS THAT THE CONDENSING UNIT ARE TO BE
 INSTALLED IN THE PARKING LOT. PLEASE SHOW THE REQUIRED
 BARRIERS FOR THE EQUIPMENT PROTECTION. FMC 303.4
  
 4) SHEET M-108: I DO NOT SEE WHERE THE MUA-1 UNIT WILL
 MEET THE 10 DEGREE DIFFERENCE WHEN HEAT WOULD BE
 REQUIRED. FMC 508.1.1. IF USING THE EXCEPTION PLEASE
 SHOW THE CALCULATIONS.
  
 5) THE HOOD DRAWINGS SHOULD NOT BE FOR REFERENCE,
 PLEASE REMOVE THIS NOTE. FBC 107.2.1
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  