| 2022-05-06 10:45:54 | 1ST REVIEW FMC |
| | PERMIT: 22021045 |
| | |
| | CODES IN EFFECT: 2020 |
| | |
| | FBC- FLORIDA BUILDING CODE |
| | FMC- FLORIDA MECHANICAL CODE |
| | FEC- FLORIDA ENERGY CONSERVATION |
| | FGC- FLORIDA FUEL GAS |
| | FEX- FLORIDA EXISTING BUILDING CODE |
| | FRC- FLORIDA RESIDENTIAL BUILDING CODE |
| | F.S.- FLORIDA STATUTES |
| | FAC- FLORIDA ACCESSIBILITY CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET M-103: THE TERMINATION LOCATION FOR THE GREASE |
| | DUCT DOES NOT MEET THE TERMINATION LOCATIONS OF FMC |
| | 506.3.13.3 |
| | 506.3.13.3 TERMINATION LOCATION. EXHAUST OUTLETS SHALL |
| | BE LOCATED NOT LESS THAN 10 FEET (3048 MM) HORIZONTALLY |
| | FROM PARTS OF THE SAME OR CONTIGUOUS BUILDINGS, |
| | ADJACENT BUILDINGS AND ADJACENT PROPERTY LINES AND |
| | SHALL BE LOCATED NOT LESS THAN 10 FEET (3048 MM) ABOVE |
| | THE |
| | ADJOINING GRADE LEVEL. EXHAUST OUTLETS SHALL BE LOCATED |
| | NOT LESS THAN 10 FEET (3048 MM) HORIZONTALLY FROM OR |
| | NOT LESS THAN 3 FEET (914 MM) ABOVE AIR INTAKE OPENINGS |
| | INTO ANY BUILDING. |
| | EXCEPTION: EXHAUST OUTLETS SHALL TERMINATE NOT LESS |
| | THAN 5 FEET (1524 MM) HORIZONTALLY FROM PARTS OF THE |
| | SAME OR CONTIGUOUS BUILDING, AN ADJACENT BUILDING, |
| | ADJACENT PROPERTY LINE AND AIR INTAKE OPENINGS INTO A |
| | BUILDING WHERE AIR FROM THE EXHAUST OUTLET DISCHARGES |
| | AWAY FROM SUCH LOCATIONS. |
| | |
| | 2) PLEASE EXPLAIN HOW TERMINATING THE GREASE DUCT INTO |
| | A PARKING LOT WOULD MEET 506.3.13.2 CREATING A PUBLIC |
| | NUISANCE. |
| | |
| | 3) IT APPEARS THAT THE CONDENSING UNIT ARE TO BE |
| | INSTALLED IN THE PARKING LOT. PLEASE SHOW THE REQUIRED |
| | BARRIERS FOR THE EQUIPMENT PROTECTION. FMC 303.4 |
| | |
| | 4) SHEET M-108: I DO NOT SEE WHERE THE MUA-1 UNIT WILL |
| | MEET THE 10 DEGREE DIFFERENCE WHEN HEAT WOULD BE |
| | REQUIRED. FMC 508.1.1. IF USING THE EXCEPTION PLEASE |
| | SHOW THE CALCULATIONS. |
| | |
| | 5) THE HOOD DRAWINGS SHOULD NOT BE FOR REFERENCE, |
| | PLEASE REMOVE THIS NOTE. FBC 107.2.1 |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM. |
| | |
| | MICHAEL EDWARDS |
| | MECHANICAL EXAMINER |