| 2022-04-04 11:56:39 | 2ND REVIEW FBC-2020 MECHANICAL |
| | PERMIT-22021045 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC- FLORIDA BUILDING CODE |
| | FMC- FLORIDA MECHANICAL CODE |
| | FEC- FLORIDA ENERGY CONSERVATION |
| | FGC- FLORIDA FUEL GAS |
| | FEX- FLORIDA EXISTING BUILDING CODE |
| | FRC- FLORIDA RESIDENTIAL BUILDING CODE |
| | F.S.- FLORIDA STATUTES |
| | FAC- FLORIDA ACCESSIBILITY CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) PLEASE PROVIDE A HOOD GREASE DUCT RISER DIAGRAM |
| | SHOWING THE GREASE DUCT DESIGN FOR ALL 3 HOOD SYSTEMS. |
| | FMC 506.3 |
| | |
| | 2) PLEASE SHOW THAT THE EF?S FOR THE HOOD SYSTEMS |
| | EXHAUST TERMINATION LOCATION IS A MINIMUM OF 3 FEET |
| | FROM THE EXTERIOR DOOR. FMC 506.3.13.2 |
| | |
| | 3) PLEASE PROVIDE A SITE SURVEY PLAN SHOWING THE GREASE |
| | DUCT TERMINATION LOCATION IS 10 FEET FROM ADJACENT |
| | BUILDINGS AND THE PROPERTY LINE. FMC 506.3.13.3 |
| | |
| | 4) PLEASE PROVIDE THE DETAILS FOR THE MUA-01, MAKE-UP |
| | AIR TEMPERATURE DOES NOT EXCEED 10 DEGREES AND PLEASE |
| | SHOW THE AIR BALANCE REPORT FOR THIS TENANT SPACE. THE |
| | MAKE UP AIR SHOULD REFLECT ALL 3 HOOD SYSTEMS. FMC 508 |
| | |
| | 5) PLEASE INDICATE IF THE WALL BEING PENETRATED BY THE |
| | EXHAUST AND MAKE UP AIR IS A RATED WALL. IF IT IS |
| | PLEASE SHOW THE PROTECTION REQUIRED. FMC 607 |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM. |
| | |