Plan Review Notes
Plan Review Notes For Permit 22021045
Permit Number 22021045
Review Stop M
Sequence Number 2
Notes
Date Text
2022-04-04 11:56:392ND REVIEW FBC-2020 MECHANICAL
 PERMIT-22021045
  
 CODES IN EFFECT:
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE PROVIDE A HOOD GREASE DUCT RISER DIAGRAM
 SHOWING THE GREASE DUCT DESIGN FOR ALL 3 HOOD SYSTEMS.
 FMC 506.3
  
 2) PLEASE SHOW THAT THE EF?S FOR THE HOOD SYSTEMS
 EXHAUST TERMINATION LOCATION IS A MINIMUM OF 3 FEET
 FROM THE EXTERIOR DOOR. FMC 506.3.13.2
  
 3) PLEASE PROVIDE A SITE SURVEY PLAN SHOWING THE GREASE
 DUCT TERMINATION LOCATION IS 10 FEET FROM ADJACENT
 BUILDINGS AND THE PROPERTY LINE. FMC 506.3.13.3
  
 4) PLEASE PROVIDE THE DETAILS FOR THE MUA-01, MAKE-UP
 AIR TEMPERATURE DOES NOT EXCEED 10 DEGREES AND PLEASE
 SHOW THE AIR BALANCE REPORT FOR THIS TENANT SPACE. THE
 MAKE UP AIR SHOULD REFLECT ALL 3 HOOD SYSTEMS. FMC 508
  
 5) PLEASE INDICATE IF THE WALL BEING PENETRATED BY THE
 EXHAUST AND MAKE UP AIR IS A RATED WALL. IF IT IS
 PLEASE SHOW THE PROTECTION REQUIRED. FMC 607
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  