Plan Review Notes For Permit 22021045
Permit Number 22021045
Review Stop FIRE
Sequence Number 2
Notes
Date Text
2022-03-22 12:41:16THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) THERE IS AN INDICATION OFEXHAUST AND INTAKES LOCATED
 ON A EXTERIOR WALL, NOT THE ROOF.
  
 PER NFPA 96
  
 7.8.3 WALL TERMINATIONS. WALL TERMINATIONS SHALL BE
 ARRANGED
 WITH OR PROVIDED WITH THE FOLLOWING PROPERTIES:
 (1) THE TERMINATION SHALL BE THROUGH A NONCOMBUSTIBLE
 WALL
 WITH A MINIMUM OF 3 M (10 FT) OF CLEARANCE FROM THE
 OUTLET TO ADJACENT BUILDINGS, PROPERTY LINES, GRADE
 LEVEL,
 COMBUSTIBLE CONSTRUCTION, ELECTRICAL EQUIPMENT OR
 LINES,
 AND WITH THE CLOSEST POINT OF ANY AIR INTAKE OR
 OPERABLE
 DOOR OR WINDOW AT OR BELOW THE PLANE OF THE EXHAUST
 TERMINATION.
 (2) THE CLOSEST POINT OF ANY AIR INTAKE OR OPERABLE
 DOOR OR WIN DOW ABOVE THE PLANE OF THE EXHAUST
 TERMINATION SHALL BE A
 MINIMUM OF 3 M (10 FT) IN DISTANCE, PLUS 76 MM (3 IN.)
 FOR
 EACH 1 DEGREE FROM HORIZONTAL, THE ANGLE OF DEGREE
 BEING
 MEASURED FROM THE CENTER OF THE EXHAUST TERMINATION TO
 THE
 CENTER OF THE AIR INTAKE OR OPERABLE DOOR OR WINDOW, AS
 INDI CATED IN FIGURE 7.8.3.
 (3) A WALL TERMINATION IN A SECURED AREA SHALL BE
 PERMITTED TO
 BE AT A LOWER HEIGHT ABOVE GRADE IF ACCEPTABLE TO THE
 AU THORITY HAVING JURISDICTION.
 (4) THE EXHAUST FLOW SHALL BE DIRECTED PERPENDICULARLY
 OUT WARD FROM THE WALL FACE OR UPWARD.
 (5) ALL THE DUCTWORK SHALL BE PITCHED TO DRAIN THE
 GREASE BACK
 INTO THE HOOD(S) OR WITH A DRAIN PROVIDED TO BRING THE
 GREASE BACK INTO A CONTAINER WITHIN THE BUILDING OR
 INTO A
 REMOTE GREASE TRAP.
 (6) A LISTED GREASE DUCT SHALL COMPLY WITH SECTION 7.4;
 OTHER
 DUCTS SHALL COMPLY WITH SECTION 7.5.
 (7) AN APPROVED FAN SHALL MEET THE REQUIREMENTS OF
 7.8.3(5)
 AND OF 8.1.2 OR 8.1.4
  
 PLEASE PROVIDE A DETAILED HORIZONTAL VIEW OF THAT WALL
 SHOWING DIMENSIONS TO ALL WINDOWS, DOORS, OEPNINGS IN
 COMPLIANCE WITH NFPA 96.
  
 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  