| Plan Review Notes For Permit 22021014 |
| Permit Number |
22021014 |
|
| Review Stop |
M |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2022-04-25 12:56:52 | PLAN DENIED | | | 1) REFER TO SECTION M1602 RETURN AIR NUMBER 4 | | | RETURN AIR SHALL NOT BE TAKEN FROM BATHROOMS. | | | 2020 FBC RESIDENTIAL CODE. | | | 2) REFER TO SECTION 107.2.1.3 QUALITY OF PLANS | | | PLAN IS BLURRY CAN'T READ DUCT SIZE OR CFM. | | | 3) IS THE AIR CONDITIONING SYSTEM NEW OR EXISTING | | | IF NEW PLEASE PROVIDE A EQUIPMENT SCHEDULE. | | | PLAN REVIEW BY HAROLD MOSER | | | [email protected] | | | OFFICE 561-805-6732 | | | FAX 561-805-6676 | | | |
|