| 2022-04-21 09:41:01 | REMODEL |
| | REVIEWED BY ROGER MCPHERSON |
| | 561-805-6716 |
| | [email protected] |
| | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 |
| | AMENDMENT |
| | |
| | CORRECTIONS NEEDED - |
| | |
| | 1) DRAWING (ID-4) SHOW NEW CEILING HEIGHT IN THE |
| | BATHROOM AND TOILET ROOM AT 82" - MINIMUM CEILING |
| | HEIGHT IS 84" PER FBC 1208.2 MINIMUM CEILING HEIGHTS. |
| | OCCUPIABLE SPACES, HABITABLE SPACES AND CORRIDORS SHALL |
| | HAVE A CEILING HEIGHT OF NOT LESS THAN 7 FEET 6 INCHES |
| | (2286 MM) ABOVE THE FINISHED FLOOR. BATHROOMS, TOILET |
| | ROOMS, KITCHENS, STORAGE ROOMS AND LAUNDRY ROOMS SHALL |
| | HAVE A CEILING HEIGHT OF NOT LESS THAN 7 FEET (2134 MM) |
| | ABOVE THE FINISHED FLOOR. |
| | |
| | 2) DRAWING ID-00 HAS THE WRONG CODE VERSION - SHOULD BE |
| | 2020 FBC |
| | |
| | 3) FOR THE NEW FLOORING - THE FOLLOWING ACUSTICAL TEST |
| | REPORTS ARE REQUIRED: |
| | |
| | MANUFACTURER SPEC SHEETS ARE NOT ACCEPTABLE DUE TO |
| | DISCREPANCIES BETWEEN SPEC SHEETS/BROCHURES AND TEST |
| | REPORTS FOR SOME MANUFACTURERS (NOT NECESSARILY THE |
| | MANUFACTURER SELECTED; THIS IS A GENERAL COMMENT) |
| | |
| | A. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING |
| | DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR |
| | SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS |
| | (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR |
| | BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90.. |
| | PROVIDE A COPY OF THE TEST REPORT. (A DROP CEILING |
| | SHOULD NOT BE INCLUDED IN THE FLOOR/CEILING ASSEMBLY |
| | DESCRIPTION UNLESS THE UNIT MATCHES THE TESTED DROP |
| | CEILING DESCRIPTION) |
| | |
| | B. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN |
| | DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC |
| | OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN |
| | IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN |
| | 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH |
| | ASTM E 492. PROVIDE A COPY OF THE TEST REPORT. (A DROP |
| | CEILING SHOULD NOT BE INCLUDED IN THE FLOOR/CEILING |
| | ASSEMBLY DESCRIPTION UNLESS THE UNIT MATCHES THE TESTED |
| | DROP CEILING DESCRIPTION) |
| | |
| | C. FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE |
| | BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL |
| | INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID |
| | DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED |
| | TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE |
| | 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84 |
| | OR UL 723. (DO NOT NEED THIS REPORT IF THE PADDING IS |
| | ATTACHED TO THE FLOORING) |
| | |
| | YOU CAN EMAIL ME THE PROPOSED TEST REPORTS TO VERIFY |
| | THAT THEY ARE TEST REPORTS BEFORE RESUBMITTING TO |
| | PROJECTDOX ( [email protected] ) |
| | |