| Plan Review Notes For Permit 22021014 |
| Permit Number |
22021014 |
|
| Review Stop |
FIRE |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2022-03-24 10:25:15 | FIRE COMMENTS: | | | SUBMISSIONS DID NOT ADDRESS PREVIOUS COMMENTS ON THE | | | PLAN SET FOR: | | | 1) PROVIDE DETAIL ON ANY PENETRATIONS INTO A FIRE RATED | | | WALL AND HOW THE RATING WILL BE MAINTAINED. NFPA 101, | | | 8.3.2 | | | 2) PROVIDE INFORMATION ON THE TESTING OF ALL FLOORING | | | MATERIALS TO BE INSTALLED AND THE ACOUSTIC UNDERLAYMENT | | | FOR FIRE PERFORMANCE INCLUDING THE CRITICAL RADIANT | | | FLUX OF THE MATERIALS. NFPA 101, 10.2.7 | | | 3) ALL FIRE SPRINKLER AND/OR FIRE ALARM SYSTEMS SHALL | | | BE MAINTAINED OPERATIONAL AT ALL TIMES DURING DEMO AND | | | CONSTRUCTION AND ANY IMPAIRMENT THAT EXCEEDS 4 HOURS OF | | | CONTINUOUS DURATION WILL REQUIRE A FIRE WATCH TO BE | | | IMPLEMENTED. NFPA 1, 16.4.4 | | | 4) ALL FIRE ALARM AND/OR FIRE SPRINKLER WORK REQUIRES | | | SEPARATE PERMITS AND SHOP DRAWINGS TO BE SUBMITTED, | | | REVIEWED AND APPROVED PRIOR TO ANY WORK ON THESE LIFE | | | SAFETY SYSTEMS BY QUALIFIED CONTRACTORS. | | | CHARLES R. WALKER, SENIOR FIRE INSPECTOR | | | 561-804-4762 | | | [email protected] | | | |
|