| 2022-03-03 11:10:38 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1 |
| | WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL |
| | MANUAL REVISED 2017 |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 |
| | 7TH EDITION |
| | FBC EX = FLORIDA EXISTING BUILDING CODE 2020 7TH |
| | EDITION |
| | FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION |
| | FAC= FLORIDA ADMINISTRATIVE CODE |
| | FS = FLORIDA STATUTES |
| | |
| | 22021014 2427 PRESIDENTIAL WAY # 404 |
| | |
| | 1ST REVIEW |
| | |
| | PLUMBING COMMENTS: DENIED |
| | |
| | 1. PLAN SHEET P301 |
| | ...A) REGARDING NOTES 208, 209 AND 210: PER WPB FBC |
| | 107.2.1, PROVIDE COMPLIANT SANITARY RISER DIAGRAM FOR |
| | EACH NEW SHOWER INSTALLATION. TO SHOW COMPLIANCE WITH |
| | FBC PL CHAPTERS 7, 9 AND 10, SHOW FIXTURE DRAINS, |
| | APPLICABLE BRANCH AND/OR STACK CONNECTIONS, TRAPS AND |
| | VENTING; INCLUDE SIZES. |
| | ...B) REGARDING NOTE 206: PER WPB FBC 107.2.1, ADD TO |
| | NOTE "THE WASTE CONNECTION OF A RESIDENTIAL DISHWASHER |
| | SHALL CONNECT DIRECTLY TO A WYE BRANCH FITTING ON THE |
| | TAILPIECE OF THE KITCHEN SINK, DIRECTLY TO THE |
| | DISHWASHER CONNECTION OF A FOOD WASTE DISPOSER, OR |
| | THROUGH AN AIR BREAK TO A STANDPIPE. THE WASTE LINE OF |
| | A RESIDENTIAL DISHWASHER SHALL RISE AND BE SECURELY |
| | FASTENED TO THE UNDERSIDE OF THE SINK RIM OR COUNTER |
| | TOPPER FBC PL 409.4." |
| | ...C) REGARDING NOTE 203: PER WPB FBC 107.2.1, PROVIDE |
| | CROSS SECTION SHOWER THRESHOLD/LINER/WALL DETAIL AS |
| | FOLLOWS: |
| | ......1) FBC PL 421.4.1: WALLS IN SHOWER COMPARTMENTS |
| | SHALL BE CONSTRUCTED OF SMOOTH, CORROSION-RESISTANT AND |
| | NONABSORBENT WATERPROOF MATERIALS NOT LESS THAN 6 FEET |
| | ABOVE THE ROOM FLOOR LEVEL, AND NOT LESS THAN 70 INCHES |
| | ABOVE THE DRAIN OF THE SHOWER. |
| | ......2) FBC PL 421.4.1 AND 421.5: FLOOR SURFACES SHALL |
| | BE CONSTRUCTED OF IMPERVIOUS, NONCORROSIVE, |
| | NONABSORBENT AND WATERPROOF MATERIALS |
| | ......3) FBC PL 421.5.2: LINERS SHALL TURN UP ON ALL |
| | SIDES NOT LESS THAN 2 INCHES ABOVE THE FINISHED |
| | THRESHOLD LEVEL |
| | ......4) FBC PL 421.5.2: LINERS SHALL BE RECESSED AND |
| | FASTENED TO AN APPROVED BACKING |
| | ......5) FBC PL 421.5.2: LINERS SHALL NOT BE NAILED OR |
| | PERFORATED AT ANY POINT LESS THAN 1 INCH ABOVE THE |
| | FINISHED THRESHOLD |
| | ......6) FBC PL 421.5.2: LINERS SHALL BE PITCHED |
| | ONE-FOURTH UNIT VERTICAL IN 12 UNITS HORIZONTAL |
| | (2-PERCENT SLOPE) AND SHALL BE SLOPED TOWARD THE |
| | FIXTURE DRAIN |
| | ......7) FBC PL 421.5.2: LINERS SHALL BE SECURELY |
| | FASTENED TO THE WASTE OUTLET AT THE SEEPAGE ENTRANCE, |
| | MAKING A WATER-TIGHT JOINT BETWEEN THE LINER AND THE |
| | OUTLET |
| | ......8) FBC PL 421.5: FLOORS OR RECEPTORS UNDER SHOWER |
| | COMPARTMENTS SHALL BE LAID ON, AND SUPPORTED BY, A |
| | SMOOTH AND STRUCTURALLY SOUND BASE. |
| | ......9) FBC PL 421.5.2: LINER MATERIAL (SPECIFY LINER |
| | MATERIAL COMPLYING WITH ONE OF THE FOLLOWING FBC PL |
| | SECTIONS-421.5.2.1, 421.5.2.2, 421.5.2.3, 421.5.2.4, |
| | 421.5.2.5 OR 421.5.2.6.) NOTE THAT FBC PL 421.5.2.1 |
| | PLASTICIZED POLYVINYL CHLORIDE (PVC) SHEETS MEETING THE |
| | REQUIREMENTS OF ASTM D4551 IS A COMMON LINER USED. |
| | ...D) REGARDING NOTE 201: NOTE IS UNCLEAR. ARE TWO NEW |
| | LAVATORIES REPLACING ONE EXISTING LAVATORY OR TWO |
| | EXISTING LAVATORIES? PER WPB FBC 107.2.1, CLARIFY. IF |
| | TWO ARE REPLACING ONE, THEN PER WPB FBC 107.2.1, |
| | PROVIDE SANITARY RISER DIAGRAM SHOWING THE NEW |
| | CONFIGURATION AND COMPLIANCE WITH FBC PL SECTIONS 909, |
| | 911. |
| | ...E) PER WPB FBC 107.2.1, TO SHOW COMPLIANCE WITH FBC |
| | PL 704.1, PROVIDE NOTE STATING "HORIZONTAL DRAINAGE |
| | PIPING LESS THAN 3 INCH DIAMETER SHALL HAVE A MINIMUM |
| | SLOPE OF 1/4 INCH PER FOOT. 3 INCH TO 6 INCH DIAMETER |
| | SHALL HAVE A MINIMUM SLOPE OF 1/8 INCH PER FOOT." |
| | |
| | 2.PLAN SHEET P401: |
| | ...A) REGARDING NOTE 110: PER WPB FBC 107.2.1, PROVIDE |
| | THE FOLLOWING NOTES. |
| | ......1) MANUFACTURER'S SPECIFICATION/INSTALLATION |
| | MANUALS FOR THE HAND-HELD SHOWERS AND THE INDIVIDUAL |
| | SHOWER VALVES SHALL BE ON SITE FOR INSPECTION. |
| | ......2) HAND-HELD SHOWERS SHALL CONFORM TO ASME |
| | A112.18.1/CSA B125.1. HAND-HELD SHOWERS SHALL PROVIDE |
| | BACKFLOW PROTECTION IN ACCORDANCE WITH ASME |
| | A112.18.1/CSA B125.1 OR SHALL BE PROTECTED AGAINST |
| | BACKFLOW BY A DEVICE COMPLYING WITH ASME A112.18.3 PER |
| | FBC PL 412.2. |
| | ......3) INDIVIDUAL SHOWER AND TUB-SHOWER COMBINATION |
| | VALVES SHALL BE BALANCED-PRESSURE, THERMOSTATIC OR |
| | COMBINATION BALANCED-PRESSURE/THERMOSTATIC VALVES THAT |
| | CONFORM TO THE REQUIREMENTS OF ASSE 1016/ASME |
| | A112.1016/CSA B125.16 OR ASME A112.18.1/CSA B125.1 AND |
| | SHALL BE INSTALLED AT THE POINT OF USE. SHOWER AND |
| | TUB-SHOWER COMBINATION VALVES REQUIRED BY THIS SECTION |
| | SHALL BE EQUIPPED WITH A MEANS TO LIMIT THE MAXIMUM |
| | SETTING OF THE VALVE TO 120DEGREES F, WHICH SHALL BE |
| | FIELD ADJUSTED IN ACCORDANCE WITH THE MANUFACTURE'S |
| | INSTRUCTIONS. IN-LINE THERMOSTATIC VALVES SHALL NOT BE |
| | UTILIZED FOR COMPLIANCE WITH THIS SECTION PER FBC PL |
| | 412.3. |
| | |
| | 3. PLAN SHEET P801/WATER HEATER SCHEDULE: SCHEDULED |
| | A.O. SMITH PNLB-50 APPEARS TO HAVE BEEN REPLACED BY |
| | ENLB 50. PER WPB FBC 107.2.1, PROVIDE MANUFACTURER'S |
| | SPECIFICATION/INSTALLATION MANUALS FOR THE WATER |
| | HEATER; |
| | ...A) HIGHLIGHT THE CORRECT MODEL NUMBER |
| | ...B) PROVIDE NOTE STATING MANUFACTURER'S |
| | SPECIFICATION/INSTALLATION MANUALS FOR THE WATER HEATER |
| | SHALL BE SHALL BE ON SITE FOR INSPECTION. |
| | |
| | 4.WATER HEATER SCHEDULE & DETAIL- PROVIDE DETAIL OF |
| | WATER HEATER SHOWING HEATER W/STORAGE CAPACITY, PIPING |
| | INCLUDING CW, HW, VALVES (INCLUDING VACUUM RELIEF VALVE |
| | IF APPLICABLE FBC PL 504.2) , THERMAL EXPANSION CONTROL |
| | DEVICE (INCLUDING SIZE), T&P DISCHARGE (INCLUDING |
| | TERMINATION) AND WATER HEATER PAN AND DRAIN (INCLUDING |
| | TERMINATION) PER WPB FPC 107.2.1; COMPLY WITH FBC PL |
| | 607.3, 503.1, 504.1, 504.4, 504.4.1, 504.5, 504.6, |
| | 504.7, 504.7.1 AND 504.7.2. PLEASE NOTE THAT PER FBC PL |
| | 504.7.2, WHERE A PAN DRAIN WAS NOT PREVIOUSLY |
| | INSTALLED, A PAN DRAIN SHALL NOT BE REQUIRED FOR A |
| | REPLACEMENT WATER HEATER INSTALLATION. IF THIS IS THE |
| | CASE, PLEASE INDICATE SUCH ON THE DETAIL. |
| | |
| | 5.ALL COMPONENTS IN THE DOMESTIC WATER SYSTEM SHALL BE |
| | LEAD FREE IN ACCORDANCE WITH FBC PL 605.2 AND 605.2.1. |
| | PER WPB FBC 107.2.1, PROVIDE NOTE ON PLANS STATING THE |
| | SAME. |
| | |
| | 6.PER WPB FBC 107.2.1, PROVIDE PIPE HANGER DETAIL FOR |
| | ADDED SHOWER FIXTURE DRAINS WITH A NOTE STATING, |
| | "HORIZONTAL PIPE SHALL BE SUPPORTED IN ACCORDANCE WITH |
| | FBC PL TABLE 308.5." |
| | |
| | 7.PER WPB FBC 107.2.1, PROVIDE RATED UL FLOOR |
| | PENETRATION ASSEMBLY DETAIL FOR THE NEW SHOWER DRAIN |
| | PENETRATIONS COMPLYING WITH FBC CHAPTER 7. |
| | |
| | |
| | END OF COMMENTS. |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED |
| | AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS. |
| | |
| | |
| | JERALD SMITH |
| | PLUMBING PLANS EXAMINER PX928 |
| | CITY OF WEST PALM BEACH |
| | EMAIL [email protected] |
| | MOBILE 561-246-0882 |
| | PLEASE NOTE THAT I TYPICALLY WORK ON TUESDAYS AND |
| | THURSDAYS |
| | |
| | 22021014 2427 PRESIDENTIAL WAY # 404 |
| | |
| | |
| | |