Plan Review Notes
Plan Review Notes For Permit 22021006
Permit Number 22021006
Review Stop P
Sequence Number 1
Notes
Date Text
2022-03-31 06:33:001ST PLUMBING REVIEW
  
 V7 FPC - 2020 FLORIDA PLUMBING CODE
 V7 FGC - 2020 FLORIDA FUEL GAS
 V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE
 V7 FEC - 2020 FLORIDA ENERGY CONSERVATION
 2021 F.S. - 2021 FLORIDA STATUTES
 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE
 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE
 FBC CHAPTER 1
  
 THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED
 BY RYAN BROWN WITH THE FOLLOWING COMMENTS.
  
  
 1. PAGE P001, COMMENT #1 AND #10 - 2017 WPB AMEND 107.3
 - REFERENCE TO THE 2014 FPC NEEDS TO BE CURRENT CODE
 CYCLE. PLEASE CHANGE TO 2020 FPC.
  
 2. PAGE P001 - WATER HEATER DETAIL - 2020 FPC - 607.1.1
 TEMPERATURE LIMITING MEANS - THE THERMOSTAT ON THE
 WATER HEATER CANNOT BE THE LIMIT FOR HOT WATER
 DELIVERY. PLEASE PROVIDE A DETAIL FOR SOMETHING OTHER
 THAN THE THERMOSTAT ON THE WATER HEATER EITHER AT THE
 WATER HEATERS OR AT EACH FIXTURE. THIS IS IN ADDITION
 TO THE PROTECTION FOR TEMPERED WATER.
  
 3. PAGE P501 - 2020 FPC 1003.3.1 - GREASE INTERCEPTORS
 AND AUTOMATIC GREASE REMOVAL DEVICES SHALL RECEIVE
 WASTE ONLY FROM FIXTURES AND EQUIPMENT THAT ALLOW FATS,
 OILS OR GREASE TO BE DISCHARGED. HAND SINKS INTENDED
 FOR HAND WASHING DO NOT RECEIVE GREASE WASTE AND SHALL
 NOT DISCHARGE TO THE GREASE WASTE.
  
 4. PERMITTING - 2017 WPB AMEND - 107.3 DUE TO A CHANGE
 IN PROCESS, THE BACKFLOW PERMIT AND GREASE INTERCEPTOR
 PERMITS ARE REQUIRED TO BE SUBMITTED PRIOR TO ISSUANCE
 OF THE PRIMARY PERMIT (AS APPLICABLE). YOU CAN SUBMIT
 AN APPLICATION (TBD - TO BE DETERMINED) IF YOU DO NOT
 HAVE A CONTRACTOR SELECTED BY EMAILING A COMPLETED
 PERMIT APPLICATION TO [email protected] . YOU
 WILL RECEIVE INSTRUCTIONS TO PAY FEES AND UPLOAD PLANS.
 YOU MAY UPLOAD PLANS AND PAY FEES AT A FUTURE DATE, BUT
 THE APPLICATION IS REQUIRED AT THIS TIME. WE RECOMMEND
 THAT YOU PAY FEES AND UPLOAD PLANS AT THE SAME TIME.
 AFTER YOU HAVE THE PERMIT(S) GENERATED, NOTIFY ME VIA
 EMAIL AND I WILL CHANGE THE REVIEW STATUS TO PASS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
  
 RYAN W. BROWN