Plan Review Notes For Permit 22021006
Permit Number 22021006
Review Stop M
Sequence Number 1
Notes
Date Text
2022-04-04 17:08:001ST REVIEW FBC-2020 MECHANICAL
 PERMIT-22021006
  
 CODES IN EFFECT:
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET A-050.00: UNDER THE CODE DATA INFORMATION,
 PLEASE PROVIDE THE CURRENT 2020 FBC CODES.
  
 2) PLEASE ADD A NOTE TO THE MECHANICAL DRAWING
 INDICATING THAT THE KITCHEN HOODS AND ASSOCIATED
 DUCTWORK WILL NOT BE REVIEWED UNDER THIS PERMIT AS THIS
 WILL BE REQUIRED TO HAVE A SEPARATE PERMIT AND REVIEW.
  
 3) PLEASE PROVIDE THE MECHANICAL EQUIPMENT SIZING
 CALCULATIONS. FEC C403.2.1
  
 4) PLEASE PROVIDE A MECHANICAL DEMO DRAWING AND A
 COMPLETE SCOPE OF WORK FOR THE MECHANICAL DEMOLITION.
 FBC 107.2.1
  
 5) PLEASE PROVIDE THE OUTDOOR AIR CALCULATIONS BASED ON
 EACH USE OF SPACE ACCORDING TO FMC 403.3.1.1 AND TABLE
 403.3.1.1.
  
 6) PLEASE PROVIDE AN AIR BALANCE REPORT FOR THIS TENANT
 SPACE. FMC 508
  
 7) PLEASE SHOW THE MAKEUP AIR MEETS THE 10 DEGREE TEMP
 DIFFERENCE OR SHOW THE CALCULATIONS THAT THE MECHANICAL
 SYSTEM IS SIZED TO HANDLE THE LOAD. FMC 508.1.1
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  