| 2022-04-04 17:08:00 | 1ST REVIEW FBC-2020 MECHANICAL |
| | PERMIT-22021006 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC- FLORIDA BUILDING CODE |
| | FMC- FLORIDA MECHANICAL CODE |
| | FEC- FLORIDA ENERGY CONSERVATION |
| | FGC- FLORIDA FUEL GAS |
| | FEX- FLORIDA EXISTING BUILDING CODE |
| | FRC- FLORIDA RESIDENTIAL BUILDING CODE |
| | F.S.- FLORIDA STATUTES |
| | FAC- FLORIDA ACCESSIBILITY CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET A-050.00: UNDER THE CODE DATA INFORMATION, |
| | PLEASE PROVIDE THE CURRENT 2020 FBC CODES. |
| | |
| | 2) PLEASE ADD A NOTE TO THE MECHANICAL DRAWING |
| | INDICATING THAT THE KITCHEN HOODS AND ASSOCIATED |
| | DUCTWORK WILL NOT BE REVIEWED UNDER THIS PERMIT AS THIS |
| | WILL BE REQUIRED TO HAVE A SEPARATE PERMIT AND REVIEW. |
| | |
| | 3) PLEASE PROVIDE THE MECHANICAL EQUIPMENT SIZING |
| | CALCULATIONS. FEC C403.2.1 |
| | |
| | 4) PLEASE PROVIDE A MECHANICAL DEMO DRAWING AND A |
| | COMPLETE SCOPE OF WORK FOR THE MECHANICAL DEMOLITION. |
| | FBC 107.2.1 |
| | |
| | 5) PLEASE PROVIDE THE OUTDOOR AIR CALCULATIONS BASED ON |
| | EACH USE OF SPACE ACCORDING TO FMC 403.3.1.1 AND TABLE |
| | 403.3.1.1. |
| | |
| | 6) PLEASE PROVIDE AN AIR BALANCE REPORT FOR THIS TENANT |
| | SPACE. FMC 508 |
| | |
| | 7) PLEASE SHOW THE MAKEUP AIR MEETS THE 10 DEGREE TEMP |
| | DIFFERENCE OR SHOW THE CALCULATIONS THAT THE MECHANICAL |
| | SYSTEM IS SIZED TO HANDLE THE LOAD. FMC 508.1.1 |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM. |
| | |