Plan Review Notes
Plan Review Notes For Permit 22021006
Permit Number 22021006
Review Stop B
Sequence Number 1
Notes
Date Text
2022-04-13 14:10:15WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 22021006
 ADD: 413 S ROSEMARY # 181 (HARRY'S)
 CONT: SHAWMUT WOODWORKING AND SUPPLY
 TEL: 617-352-4380
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: WED. APRIL 13TH/ 2022
 ACTION: DENIED
  
 1) CITY PLACE MANAGEMENT STAMP OF APPROVAL. THE CITY
 PLACE RETAIL MANAGEMENT APPROVAL STAMP IS REQUIRED ON
 THE PLANS. FOR AN ALTERNATE, YOU MAY PROVIDE A LETTER
 FROM CITY PLACE RETAIL MANAGEMENT WHICH APPROVES THE
 SPECIFIC PLANS SUBMITTED UNDER THIS PERMIT.
  
 2A) SHEET 000.00 THE COVERSHEET UNDER THE HEADING OF
 PROJECT INFORMATION (4) LIST AUTHORITY RELEVANT
 BUILDING CODE AS THE FLORIDA BUILDING CODE (FAMILY OF
 CODES) 6TH EDITION (2017) AS THE CURRENT CODE BEING
 ENFORCED. PLEASE NOTE THE 7TH EDITION OF THE FLORIDA
 BUILDING CODES (FAMILY OF CODES) 2020 EDITION WAS
 ADOPTED STATE-WIDE ON DEC. 31ST/ 2020. PLEASE CORRECT
 THE CODE REFERENCES.
  
 2B) SHEET 000.00 THE COVERSHEET UNDER THE HEADING OF
 PROJECT INFORMATION (7) LIST THE PROJECT OCCUPANCY
 CLASSIFICATION AS, A-2, F-2, & M. FOR THE F-2 OCCUPANCY
 CLASSIFICATION LEASE PROVIDE WHAT TYPE OF ACTIVITY
 REQUIRES THIS OCCUPANCY CLASSIFICATION. COMMERCIAL
 KITCHENS NOT AFFILIATED WITH RESTAURANTS OR SIMILAR
 DINING FACILITIES AND MORE 2,500 SQUARE FEET IN AREA
 ARE CLASSIFIED AS A F-1 OCCUPANCY. SEE 2020
 FBC-BUILDING CODE SECTION 306.2.
  
 2C) SHEET 000.00 THE COVERSHEET UNDER THE HEADING OF
 PROJECT INFORMATION (7) LIST THE PROJECT OCCUPANCY
 CLASSIFICATION AS, A-2, F-2, & M. WHY IS A MERCANTILE
 OCCUPANCY LISTED AS AN OCCUPANCY GROUP? THE LIFE SAFETY
 PLAN DOES NOT SHOW ANY SALES TABLES NOR KIOSK? TO BE
 CONSIDERED ACCESSORY OCCUPANCY. THE AGGREGATE ACCESSORY
 OCCUPANCIES SHALL NOT OCCUPY MORE THAN 10 % OF THE
 FLOOR AREA (508.2.3) OTHERWISE IT IS CONSIDERED A MIXED
 USE 508.1 OF THE 2020 FBC-BUILDING CODE.
  
 2D) SHEET 000.00 THE COVERSHEET UNDER THE HEADING OF
 PROJECT INFORMATION (6) SHOULD TIE TO THE (8) ZONING
 USE GROUP.
  
 2E) I BELIEVE THIS PORTION OF THE BUIILDING IS 6
 STORIES TALL AND THE REMAINDER OF THE BUILDING IS
 18VERSES 20 STORIES. THIS TENANT SPACE IS THE 1ST
 BUILD-OUT OF SHELL SPACE AND IS CONSIDERED NEW WORK.
 PLEASE REMOVE ALL REFERENCES TO THE 2020 EXISTING
 BUILDING CODE ON ALL PLANS.
  
 3) SHEET GROUND FLOOR LIFE SAFETY PLAN:
 3A) CODE DATA APPLICABLE CODES STATES THE BUILDING CODE
 AS THE FLORIDA BUILDING CODE (FAMILY OF CODES) 6TH
 EDITION (2017) AS THE CURRENT CODE BEING ENFORCED.
 PLEASE NOTE THE 7TH EDITION OF THE FLORIDA BUILDING
 CODES (FAMILY OF CODES) 2020 EDITION WAS ADOPTED
 STATE-WIDE ON DEC. 31ST/ 2020. PLEASE CORRECT THE CODE
 REFERENCES.
  
 3B) THE LIFE SAFETY PLAN SHOWS 2 ACCESSIBLE SEATS AT
 THE BAR. THERE IS NO CUT SECTION THROUGH THE BAR
 SHOWING COMPLIANCE WITH SECTION 902.3 HEIGHT OF THE
 2020 FBC-ACCESSIBILITY CODE. THE TOPS OF DINING
 SURFACES AND WORK SURFACES SHALL BE 28 INCHES MINIMUM
 AND 34 INCHES MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
  
 3C) NOTE ONLY, NO ACTION REQUIRED. DEFERRED SUBMITTALS/
 COMPONENTS AND CLADDING PRODUCT APPROVALS.
  
 4) S-000.10 COMPONENT & CLADDING CHART FOR BUILDING
 HEIGHTS < 60 FT. THE CHART HAS BOTH VULT AND VASD,
 THANK YOU. WHAT IS A BIT CONCERNING NEITHER THE WALL
 ZONES NOR ROOF ZONES ACTUALLY STATE WALL ZONES 4 & 5,
 ROOF ZONES, 1, 2, & 3, IT IS ASSUMED WHERE THE
 TRIBUTARY SQ. FEET START AND STOP FOR EACH ZONE?
 2020 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION 107.2.1.
 DRAWINGS & SPECIFICATIONS SHALL CONTAIN INFORMATION, IN
 THE FORM OF NOTES OR OTHERWISE, AS TO THE QUALITY OF
 MATERIALS, WHERE QUALITY IS ESSENTIAL TO CONFORMITY
 WITH THE TECHNICAL CODES. SUCH INFORMATION SHALL BE
 SPECIFIC TO THE TECHNICAL CODES.
  
 5) S-101.00 & S3.00 BOTH SHOW DETAILS FOR BOLTED AND
 WELDED STEEL CONNECTIONS. THIS BUILDING CONTAINS EITHER
 BOLTED AND OR WELDED CONNECTIONS. THE CONTRACTOR IS
 REQUIRED TO PROVIDE WELD PROCEDURE SPECIFICATIONS &
 WELDER OPERATOR PERFORMANCE QUALIFICATION RECORDS IN
 ACCORDANCE WITH THE REFERENCED STANDARDS AT TIME OF
 INSPECTION FOR FIELD WIELDING, ON THE JOB-SITE
 WIELDING. THIRD PARTY CERTIFICATION WILL BE REQUIRED.
 THE OWNER MAY JUST HIRE A 3RD PARTY ENGINEERING FIRM TO
 COMPLETE AND APPROVE THE FORMER INSPECTIONS. REPORTS
 SUBMITTED TO BUILDING INSPECTOR AT TIME OF FRAMING
 INSPECTION.
 2020 FBC-B 2204.1 WELDING
 1. WELD PROCEDURES SPECIFICATIONS
 2. QUALIFICATIONS OF WELDING PERSONAL
 2017 FBC-B 2204.2 BOLTING.
 IF FURTHER CLARIFICATION AND OR QUESTIONS IS REQUIRED,
 PLEASE CONTACT THE ACTING CHIEF BUILDING INSPECTOR
 RICHARD BRUNELLE AT 561-805-6670.
  
 6) SHEET A-514. THE DETAIL SHOWS A 2HR. RATED
 MECHANICAL SPACE FOR KX FAN, THIS ROOM IS MEANT TO
 PROVIDE DUCT WRAPPED RATING FROM THE COOKING HOODS TO
 THE EXTERIOR LOUVER AT THE FACE OF THE BUILDING.
 NOTED THIS SHOULD COME IN AS:
 2020 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION 104.11 ALTERNATIVE
 MATERIALS, DESIGN AND METHODS OF CONSTRUCTION AND
 EQUIPMENT.
  
 THE PROVISIONS OF THIS CODE ARE NOT INTENDED TO PREVENT
 THE INSTALLATION OF ANY MATERIAL OR TO PROHIBIT ANY
 DESIGN OR METHOD OF CONSTRUCTION NOT SPECIFICALLY
 PRESCRIBED BY THIS CODE, PROVIDED THAT ANY SUCH
 ALTERNATIVE HAS BEEN APPROVED. AN ALTERNATIVE MATERIAL,
 DESIGN OR METHOD OF CONSTRUCTION SHALL BE APPROVED
 WHERE THE BUILDING OFFICIAL FINDS THAT THE PROPOSED
 DESIGN IS SATISFACTORY AND COMPLIES WITH THE INTENT OF
 THE PROVISIONS OF THIS CODE, AND THAT THE MATERIAL,
 METHOD OR WORK OFFERED IS, FOR THE PURPOSE INTENDED, AT
 LEAST THE EQUIVALENT OF THAT PRESCRIBED IN THIS CODE IN
 QUALITY, STRENGTH, EFFECTIVENESS, FIRE RESISTANCE,
 DURABILITY AND SAFETY. WHEN ALTERNATE LIFE SAFETY
 SYSTEMS ARE DESIGNED, THE SFPE ENGINEERING GUIDE TO
 PERFORMANCE- BASED FIRE PROTECTION ANALYSIS AND DESIGN
 OF BUILDINGS, OR OTHER METHODS APPROVED BY THE BUILDING
 OFFICIAL MAY BE USED. THE BUILDING OFFICIAL SHALL
 REQUIRE THAT SUFFICIENT EVIDENCE OR PROOF BE SUBMITTED
 TO SUBSTANTIATE ANY CLAIM MADE REGARDING THE
 ALTERNATIVE.
  
 104.11.1 RESEARCH REPORTS. SUPPORTING DATA, WHERE
 NECESSARY TO ASSIST IN THE APPROVAL OF MATERIALS OR
 ASSEMBLIES NOT SPECIFICALLY PROVIDED FOR IN THIS CODE,
 SHALL CONSIST OF VALID RESEARCH REPORTS FROM APPROVED
 SOURCES.
  
 104.11.2 TESTS. WHENEVER THERE IS INSUFFICIENT EVIDENCE
 OF COMPLIANCE WITH THE PROVISIONS OF THIS CODE, OR
 EVIDENCE THAT A MATERIAL OR METHOD DOES NOT CONFORM TO
 THE REQUIREMENTS OF THIS CODE, OR IN ORDER TO
 SUBSTANTIATE CLAIMS FOR ALTERNATIVE MATERIALS OR
 METHODS, THE BUILDING OFFICIAL SHALL HAVE THE AUTHORITY
 TO REQUIRE TESTS AS EVIDENCE OF COMPLIANCE TO BE MADE
 AT NO EXPENSE TO THE JURISDICTION. TEST METHODS SHALL
 BE AS SPECIFIED IN THIS CODE OR BY OTHER RECOGNIZED
 TEST STANDARDS. IN THE ABSENCE OF RECOGNIZED AND
 ACCEPTED TEST METHODS, THE BUILDING OFFICIAL SHALL
 APPROVE THE TESTING PROCEDURES. TESTS SHALL BE
 PERFORMED BY AN APPROVED AGENCY. REPORTS OF SUCH TESTS
 SHALL BE RETAINED BY THE BUILDING OFFICIAL FOR THE
 PERIOD REQUIRED FOR RETENTION OF PUBLIC RECORDS.
  
 12) A TRANSMITTAL LETTER / NARRATIVE LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
  
 MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM
 PART-TIME/ SEMI-RETIRED.
  
 IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET
 BACK INTO THE OFFICE CALL
 (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL.
 THANK YOU.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  