| Plan Review Notes For Permit 22020991 |
| Permit Number |
22020991 |
|
| Review Stop |
FIRE |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2022-03-30 10:47:29 | FIRE REVIEW COMMENTS: | | | THE NEW DOUBLE DOOR INSTALLATION MAY REQUIRE A FIRE | | | RESISTANCE RATING AND SELF-CLOSING DEVICES WITH | | | POSITIVE LATCHING. PROVIDE DOCUMENTATION THAT THE NEW | | | DOOR ASSEMBLY PROVIDES ADEQUATE PROTECTION IN THE | | | OPENING IN THE CMU WALL ON THE FIRST FLOOR BETWEEN THE | | | EXISTING WORK AREA AND THE EXISTING WAREHOUSE. NFPA 101 | | | 8.3.3 | | | ACKNOWLEDGE RECEIPT OF THE LETTER FROM WIGINTON FIRE | | | SYSTEMS CONCERNING COVERAGE. | | | ANY AND ALL WORK ON THE FIRE SPRINKLER AND/OR FIRE | | | ALARM SYSTEM REQUIRES SEPARATE PERMIT AND SHOP DRAWINGS | | | TO BE SUBMITTED AND APPROVED PRIOR TO ANY WORK BEING | | | CONDUCTED ON THESE SYSTEMS. | | | THE FIRE SPRINKLER AND/OR FIRE ALARM SYSTEMS MUST | | | REMAIN ACTIVE DURING ALL PHASES OF DEMOLITION AND | | | CONSTRUCTION. | | | C.R. WALKER, SENIOR FIRE INSPECTOR | | | 561-804-4762 | | | [email protected] | | | |
|