| 2022-03-02 07:47:45 | THIS PLAN WAS REVIEWED AND FAILED BY CAITLIN L. |
| | FRANCIS, FIRE INVESTIGATOR, WITH THE FOLLOWING |
| | COMMENTS: |
| | |
| | 1) PROVIDE DOOR AND WALL DETAILS FOR DOORS, ROLL UP |
| | DOORS, WALLS BEING ADDED, AND OR FILLED. |
| | |
| | 1.14.1 WHERE REQUIRED BY THE AHJ FOR NEW CONSTRUCTION, |
| | MODIFICATION, OR REHABILITATION, CONSTRUCTION DOCUMENTS |
| | AND SHOP DRAWINGS SHALL BE SUBMITTED, REVIEWED, AND |
| | APPROVED PRIOR TO THE START OF SUCH WORK AS PROVIDED IN |
| | SECTION 1.14. |
| | |
| | 2) ANY REMOVAL AND/OR CONSTRUCTION OF THE CEILING/WALL |
| | AREAS MAY REQUIRE AN EVALUATION OR MODIFICATION OF THE |
| | FIRE SPRINKLER AND FIRE ALARM SYSTEMS FOR CODE COVERAGE |
| | AND COMPLIANCE BY CERTIFIED CONTRACTORS. |
| | |
| | 3) ANY AND ALL WORK ON THE FIRE SPRINKLER AND/OR FIRE |
| | ALARM SYSTEMS SHALL BE DONE UNDER SEPARATE PERMITS AND |
| | SHOP DRAWINGS BY CERTIFIED CONTRACTORS. |
| | |
| | 4) THE FIRE SPRINKLER AND FIRE ALARM SYSTEMS SHALL |
| | REMAIN ACTIVE THROUGHOUT THE DEMO AND CONSTRUCTION |
| | PERIODS. |
| | |
| | 5) COMPLETE LIFE SAFETY PLANS FOR EACH OCCUPANCY SHALL |
| | BE PROVIDED THAT ILLUSTRATE OCCUPANT LOADS, TRAVEL |
| | DISTANCES, COMMON PATHS OF TRAVEL, DEAD-END CORRIDORS, |
| | EXIT SIGNS, EMERGENCY LIGHTING, EXITS LEADING TO A |
| | PUBLIC WAY, FIRE EXTINGUISHER LOCATIONS, AND ALL FIRE |
| | SAFETY FEATURES AND EQUIPMENT. |
| | |
| | 6) FOR THE RECORD PLEASE PROVIDE THE EXISTING EXIT |
| | SIGNS AND EMERGENCY LIGHTING FOR EVALUATION PER NFPA |
| | 101 CHAPTER 7. |
| | |
| | |
| | |