| 2022-07-25 15:46:17 | 2ND REVIEW FMC |
| | PERMIT: 22020983 |
| | |
| | CODES IN EFFECT: 2020 |
| | |
| | FBC- FLORIDA BUILDING CODE |
| | FMC- FLORIDA MECHANICAL CODE |
| | FEC- FLORIDA ENERGY CONSERVATION |
| | FGC- FLORIDA FUEL GAS |
| | FEX- FLORIDA EXISTING BUILDING CODE |
| | FRC- FLORIDA RESIDENTIAL BUILDING CODE |
| | F.S.- FLORIDA STATUTES |
| | FAC- FLORIDA ACCESSIBILITY CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) IT APPEARS THAT THIS BUILDING IS GAINING A 2ND |
| | STORY. PROVIDE DETAILS OF WHAT IS TO BE STORED IN THIS |
| | WAREHOUSE AND INCLUDE VENTILATION ACCORDING TO THE TYPE |
| | OF STORAGE. FMC 501 |
| | |
| | 2) PROVIDE THE OUTDOOR CALCULATIONS FOR THIS WAREHOUSE |
| | INCLUDING THE RP CFM/PERSON. HOW MANY PEOPLE WILL BE IN |
| | THIS WAREHOUSE? FMC TABLE 403.3.1.1 |
| | |
| | 3) THE ENERGY CALCULATIONS ARE FOR A SINGLE STORY 7278 |
| | SF WAREHOUSE WITH A MAXIMUM TONNAGE FOR THE MECHANICAL |
| | UNIT OF 4.5. THE COOLING CALCULATIONS ARE FOR A TOTAL |
| | BTU?S OF COOLING OF 154,503 BTUH WHICH IS 12.875 TONS. |
| | PLEASE BE CONSISTENT WITH BOTH CALCULATIONS. |
| | |
| | 4) PROVIDE THE ACCESS LOCATION TO THE MECHANICAL |
| | SYSTEMS ON THE DRAWING. FMC 306.5 |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM. |
| | |