| Plan Review Notes For Permit 22020983 |
| Permit Number |
22020983 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2022-08-02 13:14:39 | BUILDING ALTERATION - CHANGE OF OCCUPANCY TYPE | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected] | | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | | AMENDMENT | | | | | | CORRECTIONS NEEDED - | | | | | | 1) PLEASE PROVIDE COMPLETE (FRONT PAGES AND THE | | | INSTALLATION INSTRUCTIONS) MIAMI DADE OR FLORIDA STATE | | | PRODUCT APPROVALS FOR THE NEW EXTERIOR WINDOWS, DOORS - | | | ALL PRODUCT APPROVALS NEED TO BE REVIEWED AND MARKED | | | APPROVED BY THE BUILDING DESIGNER OF RECORD FBC WPB | | | 107.3.4 | | | | | | 2) THE EXTERIOR CONCRETE SLAB NEEDS TO CONTINUE TO | | | ALLOW FOR THE FLOOR SPACE - PLEASE SHOW ACCESSIBLE | | | ENTRY DOOR MANEUVERING SPACE (18" BESIDE THE DOOR | | | LATCH) TO COMPLY WITH FBC A 404.2.4 | | | | | | 3) THE ADDITIONAL ROOF SYSTEM ATTACHMENT ENGINEERING | | | FROM FEDERAL ENGINEERING TESTING INC. WILL NEED TO BE | | | SEPARATED FROM THE ROOFING PACKAGE TO ALLOW THE | | | ELECTRONIC SIGNATURE TO SHOW - SIGNED AND SEALED | | | DRAWINGS IN PROJECTDOX NEED TO BE | | | DIGITALLY/ELECTRONICALLY SIGNED TO BE USED IN | | | ELECTRONIC PLAN REVIEW. (A CERTIFICATE-BASED DIGITAL | | | SIGNATURE (OFTEN JUST CALLED A DIGITAL SIGNATURE) IS A | | | SPECIFIC TYPE OF E-SIGNATURE). | | | | | | | | | | | | | | | | | | | | | |
|