Plan Review Notes
Plan Review Notes For Permit 22020933
Permit Number 22020933
Review Stop P
Sequence Number 3
Notes
Date Text
2022-06-13 11:30:243RD REVIEW FBC-2020 PLUMBING
 PERMIT- 22020933
 6/13/2022
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED. FAILED COMMENTS ARE LISTED
 BELOW WITH ADDITIONAL NOTES.
  
 1) FAILED. SHEET CS-1: AN B OCCUPANT LOAD OF 62 (31
 MALE & 31 FEMALE) REQUIRES 2 MALE WATER CLOSETS AND 2
 FEMALE WATER CLOSETS- TABLE 403.1 FBC P. PLEASE NOTE
 THAT SEPARATE FACILITIES ARE REQUIRED PER SEC. 403.2
 (SEC. 403.2.1 IS NOT APPLICABLE), AND SIGNAGE IS
 REQUIRED PER 403.4. PLEASE REVISE THE PLANS
 ACCORDINGLY. THE ARCHITECT?S RESPONSE TO THE COMMENT
 AND THE CALCULATIONS BASED ON A MIXED OCCUPANY ARE NOT
 CORRECT. THE DENTIST OFFICE IS A B OCCUPANCY AND IT IS
 NOT A MIXED OCCUPANCY. THE ARCHITECT SHOULD REFER TO
 SEC. 303.1.2 AND CORRECT THE PLANS TO SHOW 2 WATER
 CLOSETS EACH FOR MALE AND FEMALE USE. THE SINGLE
 OCCUPANT UNISEX TOILET ROOM DOES NOT MEET THE MINIMUM
 REQUIRMENT.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  