| 2022-06-13 11:30:24 | 3RD REVIEW FBC-2020 PLUMBING |
| | PERMIT- 22020933 |
| | 6/13/2022 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 |
| | FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| | 2020 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. FAILED COMMENTS ARE LISTED |
| | BELOW WITH ADDITIONAL NOTES. |
| | |
| | 1) FAILED. SHEET CS-1: AN B OCCUPANT LOAD OF 62 (31 |
| | MALE & 31 FEMALE) REQUIRES 2 MALE WATER CLOSETS AND 2 |
| | FEMALE WATER CLOSETS- TABLE 403.1 FBC P. PLEASE NOTE |
| | THAT SEPARATE FACILITIES ARE REQUIRED PER SEC. 403.2 |
| | (SEC. 403.2.1 IS NOT APPLICABLE), AND SIGNAGE IS |
| | REQUIRED PER 403.4. PLEASE REVISE THE PLANS |
| | ACCORDINGLY. THE ARCHITECT?S RESPONSE TO THE COMMENT |
| | AND THE CALCULATIONS BASED ON A MIXED OCCUPANY ARE NOT |
| | CORRECT. THE DENTIST OFFICE IS A B OCCUPANCY AND IT IS |
| | NOT A MIXED OCCUPANCY. THE ARCHITECT SHOULD REFER TO |
| | SEC. 303.1.2 AND CORRECT THE PLANS TO SHOW 2 WATER |
| | CLOSETS EACH FOR MALE AND FEMALE USE. THE SINGLE |
| | OCCUPANT UNISEX TOILET ROOM DOES NOT MEET THE MINIMUM |
| | REQUIRMENT. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |