Plan Review Notes
Plan Review Notes For Permit 22020933
Permit Number 22020933
Review Stop P
Sequence Number 1
Notes
Date Text
2022-03-31 15:09:3103/30/22 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. ON SHEET A-1;
  
 A. WOULD YOU PLEASE SHOW THE CLEAR FLOOR SPACE FOR A
 SINK OF 30 INCHES X 48 INCHES PER THE 2020 FBC ACC SEC.
 602.2
  
 B. WOULD YOU PLEASE SHOW THE TURNING SPACE OF FIVE FEET
 IN BATHS 1, 2, AND 3 PER THE 603.2.1, 304.3.1 CIRCULAR
 SPACE.
  
 C. THE SERVICE SINK (MOP SINK) SURROUNDING THE WALL
 SHALL BE A NON-ABSORBENT SURFACE IN ACCORDANCE WITH THE
 2020 FBC BUILDING SEC. 1210.2.2 AND 2020 FBC SEC. P
 310.3. PLEASE MAKE A NOTE ON THIS SHEET.
  
 2. ON SHEETS A3-3;
  
 A. ON SHEET A-1, WOULD YOU PLEASE SHOW THE CLEAR FLOOR
 SPACE FOR A SINK OF 30 INCHES X 48 INCHES PER THE 2020
 FBC ACC SEC. 602.2
  
 B. WOULD YOU PLEASE SHOW THE TURNING SPACE OF FIVE FEET
 IN BATHS 1, 2, AND 3 PER THE 603.2.1, 304.3.1 CIRCULAR
 SPACE.
  
 3. ON SHEET P-1;
  
 A. WOULD YOU PLEASE SHOW THE CLEAR FLOOR SPACE FOR A
 SINK OF 30 INCHES X 48 INCHES PER THE 2020 FBC ACC SEC.
 602.2
  
 B. WOULD YOU PLEASE SHOW THE TURNING SPACE OF FIVE FEET
 IN BATHS 1, 2, AND 3 PER THE 603.2.1, 304.3.1 CIRCULAR
 SPACE.
  
 4. ON SHEET P-4, HOT WATER LINES LOOPED FOR THE
 RECIRCULATING SYSTEM ARE NOT IN A CONTINUOUS LOOP.
 THERE IS A REQUIREMENT IN THE FLORIDA ENERGY CODE SEC.
 C404.6.1. THERE IS A TABLE THAT LIMITS THE BETWEEN THE
 SOURCE AND THE OUTLET; PLEASE REFER TO TABLE 404.5.1
 FOR THE MAXIMUM ALLOWABLE PIPE LENGTH METHOD AND SIZE
 ACCORDANTLY.
  
 TEMPERED WATER SHALL BE DELIVERED FROM LAVATORIES AND
 GROUP WASH FIXTURES LOCATED IN PUBLIC TOILET FACILITIES
 PROVIDED FOR CUSTOMERS, PATRONS, AND VISITORS. TEMPERED
 WATER SHALL BE DELIVERED THROUGH AN APPROVED
 WATER-TEMPERATURE LIMITING DEVICE THAT CONFORMS TO ASSE
 1070 OR CSA B125.3 PER THE 2020 FBC SEC. 416.5 TEMPERED
 WATER FOR PUBLIC HAND-WASHING FACILITIES.
  
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND, WILL HELP EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
  
 WEST PALM BEACH AMENDMENTS 2017 FBC CHAPTER; UPON
 REQUEST.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  