| 2022-03-31 15:09:31 | 03/30/22 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS |
| | |
| | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| | TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| | |
| | 1. ON SHEET A-1; |
| | |
| | A. WOULD YOU PLEASE SHOW THE CLEAR FLOOR SPACE FOR A |
| | SINK OF 30 INCHES X 48 INCHES PER THE 2020 FBC ACC SEC. |
| | 602.2 |
| | |
| | B. WOULD YOU PLEASE SHOW THE TURNING SPACE OF FIVE FEET |
| | IN BATHS 1, 2, AND 3 PER THE 603.2.1, 304.3.1 CIRCULAR |
| | SPACE. |
| | |
| | C. THE SERVICE SINK (MOP SINK) SURROUNDING THE WALL |
| | SHALL BE A NON-ABSORBENT SURFACE IN ACCORDANCE WITH THE |
| | 2020 FBC BUILDING SEC. 1210.2.2 AND 2020 FBC SEC. P |
| | 310.3. PLEASE MAKE A NOTE ON THIS SHEET. |
| | |
| | 2. ON SHEETS A3-3; |
| | |
| | A. ON SHEET A-1, WOULD YOU PLEASE SHOW THE CLEAR FLOOR |
| | SPACE FOR A SINK OF 30 INCHES X 48 INCHES PER THE 2020 |
| | FBC ACC SEC. 602.2 |
| | |
| | B. WOULD YOU PLEASE SHOW THE TURNING SPACE OF FIVE FEET |
| | IN BATHS 1, 2, AND 3 PER THE 603.2.1, 304.3.1 CIRCULAR |
| | SPACE. |
| | |
| | 3. ON SHEET P-1; |
| | |
| | A. WOULD YOU PLEASE SHOW THE CLEAR FLOOR SPACE FOR A |
| | SINK OF 30 INCHES X 48 INCHES PER THE 2020 FBC ACC SEC. |
| | 602.2 |
| | |
| | B. WOULD YOU PLEASE SHOW THE TURNING SPACE OF FIVE FEET |
| | IN BATHS 1, 2, AND 3 PER THE 603.2.1, 304.3.1 CIRCULAR |
| | SPACE. |
| | |
| | 4. ON SHEET P-4, HOT WATER LINES LOOPED FOR THE |
| | RECIRCULATING SYSTEM ARE NOT IN A CONTINUOUS LOOP. |
| | THERE IS A REQUIREMENT IN THE FLORIDA ENERGY CODE SEC. |
| | C404.6.1. THERE IS A TABLE THAT LIMITS THE BETWEEN THE |
| | SOURCE AND THE OUTLET; PLEASE REFER TO TABLE 404.5.1 |
| | FOR THE MAXIMUM ALLOWABLE PIPE LENGTH METHOD AND SIZE |
| | ACCORDANTLY. |
| | |
| | TEMPERED WATER SHALL BE DELIVERED FROM LAVATORIES AND |
| | GROUP WASH FIXTURES LOCATED IN PUBLIC TOILET FACILITIES |
| | PROVIDED FOR CUSTOMERS, PATRONS, AND VISITORS. TEMPERED |
| | WATER SHALL BE DELIVERED THROUGH AN APPROVED |
| | WATER-TEMPERATURE LIMITING DEVICE THAT CONFORMS TO ASSE |
| | 1070 OR CSA B125.3 PER THE 2020 FBC SEC. 416.5 TEMPERED |
| | WATER FOR PUBLIC HAND-WASHING FACILITIES. |
| | |
| | WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES. |
| | A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND, WILL HELP EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA |
| | |
| | WEST PALM BEACH AMENDMENTS 2017 FBC CHAPTER; UPON |
| | REQUEST. |
| | |
| | LUIS A. CRESPO |
| | PLUMBING PLAN EXAMINER / INSPECTOR |
| | EMAIL: [email protected] OFFICE: 561 805-6720 |
| | |