| 2022-04-01 08:25:23 | 1ST REVIEW FBC-2020 MECHANICAL | | | PERMIT-22020933 | | | | | | CODES IN EFFECT: | | | | | | FBC- FLORIDA BUILDING CODE | | | FMC- FLORIDA MECHANICAL CODE | | | FEC- FLORIDA ENERGY CONSERVATION | | | FGC- FLORIDA FUEL GAS | | | FEX- FLORIDA EXISTING BUILDING CODE | | | FRC- FLORIDA RESIDENTIAL BUILDING CODE | | | F.S.- FLORIDA STATUTES | | | FAC- FLORIDA ACCESSIBILITY CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) PLEASE SHOW THAT THE MECHANICAL EQUIPMENT SIZING IS | | | DESIGNED TO MEET THE OUTPUT LOADS REQUIRED IN FEC | | | C403.2.2. THE MECHANICAL EQUIPMENT SIZING CALCULATIONS | | | INDICATE THAT THE AHU?S ARE ALL DIFFERENT IN SIZE BUT | | | THE AHU SCHEDULE ON SHEET M-1 INDICATES THE 3 AHU?S ARE | | | THE SAME 4.75 TONS. | | | | | | 2) THE STORAGE ROOMS SHOULD BE CALCULATED WITH THE AREA | | | OUTDOOR AIRFLOW RATE IN BREATHING ZONE OF .12. FMC | | | TABLE 403.3.1.1 | | | | | | 3) PLEASE PROVIDE THE CONDENSATE PIPE SIZES FOR THE | | | CONDENSATE DRAIN PIPE SYSTEM. FMC 307 | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|