| 2022-08-30 13:27:39 | JONATHAN BROOKS JR. | | | BUILDING PLANS EXAMINER | | | WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM | | | PHONE (561) 805-6656 | | | EMAIL: [email protected] | | | | | | 1ST REVIEW: FBC 2020 7TH EDITION | | | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) | | | FBC B = FBC BUILDING | | | FBC R = FBC RESIDENTIAL | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC | | | RESULTS: DENIED | | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT | | | CITY HALL, OR UPLOAD CORRECTIONS TO PROJECTDOX. | | | | | | 1. FBC B 107.2.1. REVISE SUBMITTED FASTENER DENSITY | | | CALCULATIONS PREPARED, SIGNED AND SEALED BY A FLORIDA | | | REGISTERED PROFESSIONAL ENGINEER TO INCLUDE THE CORRECT | | | PRODUCT APPROVAL/NOA FOR THE FLAT ROOF SYSTEM TO BE | | | USED. SUBMITTED POLYGLASS NOA 20-1117.03 IS AN | | | UNDERLAYMENT SYSTEM. | | | 2. PROVIDE THE FOLLOWING INFORMATION FOR THE PROPOSED | | | FLAT ROOF SYSTEM TO BE USED CORRESPONDING TO ENGINEERS | | | CALCULATIONS. COVER PAGE, EVALUATION REPORTS, | | | LIMITATIONS PAGE AND INSTALLATION INSTRUCTIONS FOR | | | SYSTEM USED. ALL APPLICABLE DETAILS AND ATTACHMENTS | | | MUST BE CLEARLY IDENTIFIED ON THE PRODUCT APPROVAL | | | DRAWINGS. | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMEMTS. | | | |
|