2022-04-12 16:10:32PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SEVENTH EDITION (2020)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) SUBMIT A ROOF DIAGRAM SHOWING THE LOCATIONS OF THE
 SOLAR PANELS. SPECIFY THE DISTANCE FROM THE ROOF EDGES
 TO THE PANELS AND THE DISTANCES FROM THE PANELS TO THE
 HIPS OR RIDGES. SPECIFY THE ROOF SLOPE, THE ROOF
 HEIGHT, ROOF SHEATHING MATERIAL (INCLUDING THICKNESS)
 AND THE ROOF COVERING MATERIAL. FBC 107.2.1
  
 2) THE WIND LOAD DRAWINGS AND WIND DATA THAT WAS
 SUBMITTED IS FOR EXPOSURE CATEGORY B, SUBMIT THE SIGNED
 AND SEALED ENGINEERING FOR EXPOSURE CATEGORY C, FBC-R
 301
  
 3) SUBMIT A PLUMBING ISOMETRIC DRAWING SPECIFYING THE
 PIPING SIZES AND LOCATION. SHOW THE LOCATIONS OF THE
 TEMPERATURE AND PRESSURE RELIEF VALVE, TEMPERATURE
 CONTROL AND OTHER SYSTEM COMPONENTS. FBC-R M2301.1
  
 4) PLEASE SUBMIT A RESPONSE LETTER INDICATING HOW EACH
 OF THE REVIEW COMMENTS HAS BEEN ADDRESSED.
  
  