| Plan Review Notes For Permit 22020815 |
| Permit Number |
22020815 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2022-07-18 14:30:44 | PLAN REVIEW COMMENTS FOR THIS REVISION | | | | | | 1ST REVIEW: THIS PROJECT IS PERMITTED UNDER THE FBC | | | FIFTH EDITION (2014) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) THESE PLANS WERE NOT REVISED TO SHOW THE MISSING | | | DOOR. IN ORDER TO AVOID CONFUSION AND MAINTAIN | | | CONSISTENCY, PLEASE CORRECT THESE PLANS. THE FLOOR | | | PLANS FOR LEVELS 17, 18 AND 19 A1.269 AND A1.269A SHOW | | | THE DOOR FROM THE FIRE LOBBY TO STAIR #2 HAS BEEN | | | ELIMINATED. FBC 3007.6.1 REQUIRES DIRECT ACCESS FROM | | | THE FIRE ACCESS LOBBY TO THE INTERIOR EXIT STAIRWAY. | | | | | | 2) NEW COMMENT. PROVIDE DETAILS/ELEVATIONS TO SHOW THAT | | | THE INDOOR BAR (0833A) ON PAGE A1.108 WILL COMPLY WITH | | | FBC ACCESSIBILITY SECTION 904. | | | | | | 3) PLEASE SUBMIT A RESPONSE LETTER INDICATING HOW EACH | | | OF THE REVIEW COMMENTS HAS BEEN ADDRESSED. | | | | | | | | | |
|