2022-07-18 14:30:44PLAN REVIEW COMMENTS FOR THIS REVISION
  
 1ST REVIEW: THIS PROJECT IS PERMITTED UNDER THE FBC
 FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THESE PLANS WERE NOT REVISED TO SHOW THE MISSING
 DOOR. IN ORDER TO AVOID CONFUSION AND MAINTAIN
 CONSISTENCY, PLEASE CORRECT THESE PLANS. THE FLOOR
 PLANS FOR LEVELS 17, 18 AND 19 A1.269 AND A1.269A SHOW
 THE DOOR FROM THE FIRE LOBBY TO STAIR #2 HAS BEEN
 ELIMINATED. FBC 3007.6.1 REQUIRES DIRECT ACCESS FROM
 THE FIRE ACCESS LOBBY TO THE INTERIOR EXIT STAIRWAY.
  
 2) NEW COMMENT. PROVIDE DETAILS/ELEVATIONS TO SHOW THAT
 THE INDOOR BAR (0833A) ON PAGE A1.108 WILL COMPLY WITH
 FBC ACCESSIBILITY SECTION 904.
  
 3) PLEASE SUBMIT A RESPONSE LETTER INDICATING HOW EACH
 OF THE REVIEW COMMENTS HAS BEEN ADDRESSED.
  
  
  