| 2022-04-28 15:10:18 | 1ST REVIEW FMC |
| | PERMIT: 22020815 |
| | |
| | CODES IN EFFECT: 2020 |
| | |
| | FBC- FLORIDA BUILDING CODE |
| | FMC- FLORIDA MECHANICAL CODE |
| | FEC- FLORIDA ENERGY CONSERVATION |
| | FGC- FLORIDA FUEL GAS |
| | FEX- FLORIDA EXISTING BUILDING CODE |
| | FRC- FLORIDA RESIDENTIAL BUILDING CODE |
| | F.S.- FLORIDA STATUTES |
| | FAC- FLORIDA ACCESSIBILITY CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) PLEASE SUBMIT THE MECHANICAL SIZING CALCULATIONS FOR |
| | ALL OF THE UNITS THAT HAVE BEEN CHANGED AS IT APPEARS |
| | THEY ARE NOW LARGER THAN THE ORIGINAL DESIGN. FEC |
| | C403.2.1 |
| | |
| | 2) SHEET M202: THE NARRATIVE OF CHANGES INDICATE THIS |
| | REVISION WAS FOR TOILET AND DRYER EXHAUST RISER |
| | DIMENSIONS/LOCATIONS. NEITHER ARE ON THIS REVISED |
| | DRAWING. |
| | |
| | 3) SHEET M202: THERE SEEMS TO BE A LAYER THAT IS |
| | MISSING FROM THIS SHEET AS AREAS ARE MISSING FROM THE |
| | LATEST DRAWING. THE FIRE LOBBY AND MECHANICAL ROOMS AT |
| | THE ELEVATOR AREA AT THE BOTTOM OF THE DRAWING AND THE |
| | CLOUD SEEMS TO HAVE COVERED UP SOME DUCTWORK AT THE TOP |
| | RIGHT OF THE SHEET. |
| | |
| | 4) PLEASE SHOW THAT THE DUCTWORK SERVING THE CORRIDORS |
| | AND THE RESIDENTIAL SUITES WILL MEET FMC 607.5.3 THE |
| | DUCT SHALL NOT HAVE OPENINGS THAT COMMUNICATE THE |
| | CORRIDOR WITH ADJACENT SPACES OR ROOMS. A FIRE DAMPER |
| | IS REQUIRED AT THE RATED CORRIDOR WALL AT EACH SUITE. |
| | |
| | 5) THE NARRATIVE FOR THESE DRAWINGS INDICATE CHANGES |
| | FOR TOILET AND DRYER EXHAUST RISER |
| | DIMENSIONS/LOCATIONS. THERE ARE NO DIMENSIONS ON THESE |
| | SHEETS. PLEASE ADD THEM OR ADD A NOTE TO THE SHEET |
| | NUMBER WHERE THEY ARE LOCATED. |
| | |
| | 6) PLEASE ADD THE LIFE SAFETY SHEETS FOR THIS PROJECT |
| | AS I NEED TO KNOW WHERE THE RATED WALL LOCATIONS ARE |
| | LOCATED OR ADD THIS LAYER TO THE MECHANICAL DRAWINGS. |
| | |
| | 7) SHEET M.707: TE/R10 SHOULD HAVE THE FIRE RATED DUCT |
| | AS WAS ON THE PREVIOUS TE /R3 IN THE SAME LOCATION. |
| | |
| | 8) SHEET M.707: PLEASE ADD NOTES FOR THE DRYER |
| | MULTISTORY EXHAUST REQUIREMENTS IN FMC 504.10 |
| | |
| | 6. THE EXHAUST FAN MOTOR SHALL BE LOCATED OUTSIDE OF |
| | THE AIRSTREAM. |
| | 7. THE EXHAUST FAN SHALL RUN CONTINUOUSLY, AND SHALL BE |
| | CONNECTED TO A STANDBY POWER SOURCE |
| | ACCORDANCE WITH SECTION 2702 OF THE FLORIDA BUILDING |
| | CODE, BUILDING. |
| | 8. EXHAUST FAN OPERATION SHALL BE MONITORED IN AN |
| | APPROVED LOCATION AND SHALL INITIATE AN AUDIBLE OR |
| | VISUAL SIGNAL WHEN THE FAN IS NOT IN OPERATION. |
| | 9. MAKEUP AIR SHALL BE PROVIDED FOR THE EXHAUST SYSTEM. |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM. |
| | |