Plan Review Notes
Plan Review Notes For Permit 22020815
Permit Number 22020815
Review Stop M
Sequence Number 1
Notes
Date Text
2022-04-28 15:10:181ST REVIEW FMC
 PERMIT: 22020815
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE SUBMIT THE MECHANICAL SIZING CALCULATIONS FOR
 ALL OF THE UNITS THAT HAVE BEEN CHANGED AS IT APPEARS
 THEY ARE NOW LARGER THAN THE ORIGINAL DESIGN. FEC
 C403.2.1
  
 2) SHEET M202: THE NARRATIVE OF CHANGES INDICATE THIS
 REVISION WAS FOR TOILET AND DRYER EXHAUST RISER
 DIMENSIONS/LOCATIONS. NEITHER ARE ON THIS REVISED
 DRAWING.
  
 3) SHEET M202: THERE SEEMS TO BE A LAYER THAT IS
 MISSING FROM THIS SHEET AS AREAS ARE MISSING FROM THE
 LATEST DRAWING. THE FIRE LOBBY AND MECHANICAL ROOMS AT
 THE ELEVATOR AREA AT THE BOTTOM OF THE DRAWING AND THE
 CLOUD SEEMS TO HAVE COVERED UP SOME DUCTWORK AT THE TOP
 RIGHT OF THE SHEET.
  
 4) PLEASE SHOW THAT THE DUCTWORK SERVING THE CORRIDORS
 AND THE RESIDENTIAL SUITES WILL MEET FMC 607.5.3 THE
 DUCT SHALL NOT HAVE OPENINGS THAT COMMUNICATE THE
 CORRIDOR WITH ADJACENT SPACES OR ROOMS. A FIRE DAMPER
 IS REQUIRED AT THE RATED CORRIDOR WALL AT EACH SUITE.
  
 5) THE NARRATIVE FOR THESE DRAWINGS INDICATE CHANGES
 FOR TOILET AND DRYER EXHAUST RISER
 DIMENSIONS/LOCATIONS. THERE ARE NO DIMENSIONS ON THESE
 SHEETS. PLEASE ADD THEM OR ADD A NOTE TO THE SHEET
 NUMBER WHERE THEY ARE LOCATED.
  
 6) PLEASE ADD THE LIFE SAFETY SHEETS FOR THIS PROJECT
 AS I NEED TO KNOW WHERE THE RATED WALL LOCATIONS ARE
 LOCATED OR ADD THIS LAYER TO THE MECHANICAL DRAWINGS.
  
 7) SHEET M.707: TE/R10 SHOULD HAVE THE FIRE RATED DUCT
 AS WAS ON THE PREVIOUS TE /R3 IN THE SAME LOCATION.
  
 8) SHEET M.707: PLEASE ADD NOTES FOR THE DRYER
 MULTISTORY EXHAUST REQUIREMENTS IN FMC 504.10
  
 6. THE EXHAUST FAN MOTOR SHALL BE LOCATED OUTSIDE OF
 THE AIRSTREAM.
 7. THE EXHAUST FAN SHALL RUN CONTINUOUSLY, AND SHALL BE
 CONNECTED TO A STANDBY POWER SOURCE
 ACCORDANCE WITH SECTION 2702 OF THE FLORIDA BUILDING
 CODE, BUILDING.
 8. EXHAUST FAN OPERATION SHALL BE MONITORED IN AN
 APPROVED LOCATION AND SHALL INITIATE AN AUDIBLE OR
 VISUAL SIGNAL WHEN THE FAN IS NOT IN OPERATION.
 9. MAKEUP AIR SHALL BE PROVIDED FOR THE EXHAUST SYSTEM.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  