| Plan Review Notes For Permit 22020815 |
| Permit Number |
22020815 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2022-05-05 08:48:38 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | FLORIDA BUILDING CODE 2017 6TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED | | | NFPA 70 2014 EDITION | | | | | | JAKE LEAHY BN, BU, PX | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | 1) FIRE ALARM REVISIONS SHALL BE SUBMITTED SEPARATELY | | | UNDER THE PERMIT FOR THE FIRE ALARM | | | | | | 2) LOW VOLTAGE REVISIONS SHALL BE AS STATED IN #1 | | | | | | 3) LOAD CALCULATIONS SHOWN ON PAGE E601-A DEMANDS DO | | | NOT MATCH UP WITH THE DEMANDS % IN THE TABLE BASED ON | | | NUMBER OF UNITS. 220.84 | | | |
|